7.1
95-8533
6-15
COMBUSTIBLE GAS SENSOR
Refer to the Combustible Gas Sensor Specification
Data sheet, form 90-1041, for specifications.
ELECTROCHEMICAL SENSORS
Refer to the Electrochemical Gas Sensor Specification
Data sheet, form 90-1079, for specifications.
Electrochemical sensors available from Det-Tronics
include Hydrogen Sulfide, Oxygen, Carbon Monoxide,
Chlorine, Sulfur Dioxide, and Nitrogen Dioxide.
EQ21xxPS POWER SUPPLY
The EQ21xxPS Rectifier / Power Supply has many
inherent advantages such as voltage regulation, high
efficiency, high power factor and short circuit
protection.
These chargers provide separate adjustable voltages
for floating or equalizing lead or nickel-cadmium cells.
An equalize switch is located on the front panel of the
charger for manual activation or a multi-mode
electronic timer can be used for automatic activation.
Steady state output voltage remains /- 1/2% of
the setting from no load to full load and for AC input
voltages /- 10% of the nominal input voltage.
The power supply is internally filtered to be no greater
than 32dBrn (“C” message weighting) and 30 millivolts
RMS for all conditions on input voltage and output
load with or without batteries connected. This allows
the A36D to be used as a battery eliminator.
Содержание DET-TRONICS 95-8533
Страница 1: ...Instructions 95 8533 Eagle Quantum Premier Fire and Gas Detection Releasing System 7 1 9 09 95 8533 ...
Страница 128: ...7 1 95 8533 A 4 Figure A 1 System Drawing 007545 001 ...
Страница 129: ...95 8533 A 5 7 1 Figure A 2 System Drawing 007545 001 ...
Страница 131: ...95 8533 7 1 B 2 Figure B 1 Drawing 007546 001 ...
Страница 132: ...95 8533 7 1 B 3 Figure B 2 Drawing 007546 001 ...
Страница 134: ...95 8533 7 1 C 2 Figure C 1 Drawing 007547 001 ...
Страница 141: ...95 8533 7 1 D 7 Figure D1 System Drawing 007545 001 ...
Страница 143: ...APPENDIX E E 1 95 8533 7 1 ...