3-31
Item
8. Release valve
control
Operation explanation and applied data, etc.
(1) SV2 gas balance control
This control is executed to balance the gas when opening SV2
while the compressor is off, in order to decrease the activation
load in the next compressor-ON time. This control is individually
executed by the master outdoor unit and each server outdoor unit.
1) Control conditions
When the compressor is switched from ON to OFF operation.
2) Contents of control
• The control point is exchanged by
△
P (Pd pressure - Ps
pressure) immediately before compressor stop.
• When
△
P
≥
P1, SV2 is opened. After SV2 has been opened,
SV2 is turned off when
△
P < P2.
• When
△
P < P1, SV2 is closed.
(MPa)
(2) SV2 high pressure release control
This control is to control pressure rising in low-frequency operation
of the inverter.
1) Control conditions
• Heating operation is performed.
(Except while defrost control is performed.)
• When No.1 compressor of the master outdoor unit only is
singly operated. (When 42Hz or lower command is output in
case of inverter unit.)
2) Contents of control
• SV2 is turned on when Pd pressure
≥
2.7MPa.
• SV2 is turned off when Pd pressure
≤
2.05MPa.
3) Stop conditions
• In stop time, thermostat OFF, defrost operation, or cooling
operation.
• When No.2 compressor of the master outdoor unit is ON.
• When even one of the terminal compressors is ON.
• When the inverter frequency command becomes 51Hz or
higher.
(3) SV2 low pressure release control
This control is to prevent quick pressure lowering in transient
operation. This control is individually executed by the master
outdoor unit and each server outdoor unit.
This control is executed as necessary except during stop time and
thermostat-OFF time.
1) Contents of control
• SV2 is opened when Ps pressure
≤
0.08 MPa
• SV2 is closed when Ps pressure > 0.12 MPa
(4) SV2 compressor case bypass control
This control is to prevent oil dilution up or 2-layers separation
status in transient operation. This control is individually executed
by the master outdoor unit and each server outdoor unit.
This control is executed during compressor-ON (except during oil
level detection controlling).
Remarks
Pd pressure
control point
P1, P2
In case of master
In case of terminal
Cooling
Master outdoor
Master outdoor
compressor OFF compressor ON
P1
P2
P1
P2
1.3
1.1
—
—
1.3
1.1
0.5
0.4
Heating
Master outdoor
compressor OFF
P1
P2
1.3
1.1
1.3
1.1
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...