3-28
Item
2. Outdoor fan
control
(Continued)
Operation explanation and applied data, etc.
(2) Heating fan control
1) Outdoor fan speed (No. of fan driving waves) is controlled
by TE sensor detection temperature.
2) If TE>20°C has been continuously detected for 5 minutes,
the operation may be stopped. In this case, the status is
same as one in usual thermostat-OFF, so restart the
operation.
3) When the high-pressure switch operates frequently under
condition of the above 2), it is considered that air filter of
the indoor unit is contaminates. Clean the filter and restart
the operation.
4) After activation, this control is not performed during the
specified time after defrost operation and defrost control.
5) When refrigerant is extremely shortened, START/STOP
operation may be repeated by this control.
3. Capacity
calculation
(3) Control for fixed-speed unit stop
The fan is driven with 1 wave to prevent stagnation of refriger-
ant into the outdoor heat exchanger.
4. Oil level
detection control
1) The volume of oil in the oil tank is judged by the detection
temperature of TK1 and TK2 sensors.
2) The present temperature detected by TK1, TK2 and TK3
sensors are stored in memory as the initial value, and then on
the solenoid valve SV3C is activated.
After then, execute sampling of TK1, TK2 and TK3 sensor
temperature, and obtain the temperature change value of TK1
and TK2. Also, whether the oil level is adequate or not is
judged from relation between the set up oil level judgment time
and the above temp. change value, and the operation
transmits to the oil equalizing control if oil is reduced.
Remarks
5
1
10
15
20
25
30
10
5
15 20 25 30
Operation capacity
(HP)
Requested capacity
(HP)
Inverter
Fixed-speed
TE temp. (˚C)
A zone : No. of lower limit waves, Compressor forced stop timer count
B zone : -2 waves/20 sec (up to No. of lower limit waves)
C zone : -1 waves/20 sec (up to No. of lower limit waves)
D zone : Hold (Held at the current No. of waves)
E zone : +1 waves/20 sec (up to Max. No. of waves)
F zone : Max. No. of waves (16 waves)
20
6
4
2
1
By the capacity request command from the indoor controller, the
inverter operation command of the master outdoor unit, ON/OFF
control of the fixed-speed compressor and the server outdoor unit
are determined. The master outdoor unit sets up activation
priority order of the server outdoor units connected to the system,
and starts the operation.
<Example of 30HP system>
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...