Check code
Operation cause
[A6]
Discharge temperature TD1 alarm
1. Outdoor unit service valve closed
2. Blockage of check valve to interrupt the liquid line.
3. Outdoor PMV A error or cooling bypass PMV B error
4. TD sensor error
5. Insufficient refrigerant, blockage in pipe
( )
( )
YES
YES
NO
YES
YES
YES
NO
YES
YES
NO
NO
NO
NO
Open service valve fully.
Repair outdoor PMV A.
Replace the check valve
Cooling bypass PMV B error
Replace TD1 sensor.
Set normal wiring.
Check miswiring of the outdoor unit
according to miswiring check function.
Check there is no blockage or pipe
breakage, and then addrefrigerant according
to judgment of refrigerant amount.
Are gas pipe,liquid pipe,
and service valve of the
outdoor unit fully open?
In there blockage in
the check valve to interrupt
the liquid line?
Is cooling bypass PMV B normal?
Is resistance characteristics
of TD1 sensor normal?
Is wiring correct?
Insufficient refrigerant,
blockage, pipe breakage.
Is outdoor PMV A normal?
1. Connector connection
2. Wiring
3. Coil
4. Valve unit
5. Outdoor P.C. board
*
In cooling
only model
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...