3-83
Check code
Operation cause
[b5]
Indoor outside input alarm
[b6]
Indoor outside interlock
1. External device error
2. Indoor main P.C. board (MCC-1361) error
Check code
Operation cause
[b7]
Secondly unit alarm in group
operating
Secondly unit error at group operating of the indoor unit
When a trouble occurred on any one of the secondly units operating in a group, an alarm is output to the
central control remote controller.
Using the remote controller of indoor unit, check a trouble on each secondly unit and take measures against
the error code.
Check code
Operation cause
[b9]
Indoor pressure sensor alarm
Output voltage error of indoor pressure sensor
There is an abnormal output voltage of indoor pressure sensor. Check disconnection of connector (CN23) of
indoor main P.C. board (MCC-1361) and output voltage of the sensor.
If the sensor is normal, replace the indoor main P.C. board. (MCC-1361)
YES
YES
NO
NO
Is outside device connected
to connector CN21 of indoor main
P.C. board (MCC-1361)?
Is outside device connected
Check cause of the operation.
Check outside device.
Defective Replacement
Check indoor main
P.C. board. (MCC-1361)
Defective Replacement
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...