3-80
Check code
Operation cause
[A7]
TS condition gas leak detection
1. Outdoor unit service valve closed
2. Blockage of check valve to interrupt the liquid line.
3. Outdoor PMV A error
4. TS sensor error
5. Insufficient refrigerant, blockage in pipe
6. 4-way valve error
YES
YES
YES
NO
NO
Open service valve fully.
Replace TS sensor.
Are gas pipe,liquid pipe,
and service valve of the
outdoor unit fully open?
YES
NO
Check and replace 4-way valve unit.
Is refrigerant bypassed from
discharge port to compressor
suction port with 4-way valve?
Is resistance characteristics
of TS sensor normal?
Insufficient refrigerant,
blockage, pipe breakage
NO
Repair outdoor PMVA.
Is outdoor PMV A normal?
1. Connector connection
2. Wiring
3. Coil
4. Valve unit
5. Outdoor P.C. board
NO
YES
YES
Replace the check valve
In there blockage in
the check valve to interrupt
the liquid line?
*
In cooling
only model
( )
Check there is no blockage or pipe
breakage, and then addrefrigerant according
to judgment of refrigerant amount.
Check code
Operation cause
[AA]
Pd sensor alarm
Pd sensor output voltage alarm
It is abnormal output voltage of Pd sensor. Check disconnection of connector connection circuit (Pd sensor :
CN501) and output voltage of the sensor.
If the sensor is normal, replace the outdoor interface P.C. board.
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...