3-60
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Check capacity decrease and appearance.
Replace IPDU P.C. board.
Replace IPDU P.C. board
and inverter compressor.
Replace IPDU P.C. board and fuse.
Modify connector of wiring.
Modify power supply line.
Is power supply voltage
of outdoor unit normal?
Is smoothing capacitor normal?
(2200µF, 400V x 2)
Is connection of
wiring connector on IPDU
P.C. board normal?
Is AC 20A fuse working?
Is inverter compressor normal?
Check IPDU P.C. board.
Check code
Operation cause
[14]
G-Tr short circuit protective system alarm
1. Outdoor unit power supply error
2. Wiring error on IPDU P.C. board
3. AC fuse disconnection
4. Inverter compressor error
5. Defective IPDU P.C. board
Check code
Operation cause
[12]
Other indoor alarm
1. Irregularity of power supply
2. Noise of peripheral equipment
3. Indoor main P.C. board failure
YES
NO
Indoor main P.C. board check
Defective Replacement
Is there no irregularity
of power supply?
Check power supply voltage,
modify lines, remove noise, etc.