3-150
252
250mm
175mm
175mm
375mm
250mm
310mm
Other 375mm
15 ± 5
1/4 Thickness
ReF No.
Quantity
Inner diameter
Cutting Dimension
252
10
2.0 mm
Cut off the 375mm (8 pcs.)
Cut off the 310mm (1 pc.)
Cut off the 250mm (1 pc.)
MMU-P0121H, P0151H. P0181H, P0241H, P0301H, P0361H, P0481H
Distributor Assembly for Exchange Method
1. Cutting dimension of capillary tubes
Distributor assembly attached capillary tubes brazed.
Please cut each as below length.
(Cutting Method)
Shave the circumference of capillary tube with a triangle file or cutter knife, then shape it.
(Caution)
Don’t deform the inner diameter of capillary tube.
2. Brazing method of joint pipe
Insert the tip of the capillary tube into the joint to 15mm depth.
Form the capillary tubes as distributor of before exchanging.
3. Brazing method to indoor heat exchanger.
Attach the brazed capillary tubes to the tip of pipe as below diagram.
(Caution)
Be careful with capillary length and insert position.