3-26
3-5. OUTLINE OF CONTROL
3-5-1. Outdoor Unit
3-5-1-1. Operation start/Operation end
The compressor, solenoid valve, pulse motor valve (PMV A), outdoor fan, etc. are controlled by a command from
the indoor controller. The server outdoor unit starts/stops by a command from the master outdoor unit.
3-5-1-2. Thermostat ON/Thermostat OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON or OFF
(By command indoor)
OFF
ON or OFF
Full
close
Full
close
Specified opening
Operation start
Operation signal from indoor
Inverter drive
Outdoor fan output
Fixed-speed MG-SW output
Each solenoid valve output
4-way valve output
(OFF in cooling operation)
PMV A output
Operation signal from indoor
Inverter drive
Outdoor fan output
Fixed-speed MG-SW output
Each solenoid valve output
4-way valve output
(OFF in cooling operation)
PMV A output
Operation stop
OFF
ON
OFF
ON
ON
OFF
ON or OFF
(By command indoor)
OFF
ON or OFF
Full
close
Full
close
Specified opening
Thermostat ON
Thermostat OFF
2 minutes and
30 seconds
2 minutes and
30 seconds