3-73
Check code
Operation cause
[96]
Consistency detection of indoor
and outdoor addresses
1. Connection error of communication cable (PQ) between
indoor and outdoor
2. Abnormal No. of connected indoor units
3. Wiring connection error of central management remote
controller
NO
YES
YES
NO
NO
YES
YES
NO
Modify connection of wiring.
Modify communication cable.
Is No.of indoor units connected
to outdoor unit normal?
Is wiring connection
to communication cable
P.Q normal?
Is communication cable
connected to another
outdoor unit incorrectly?
Is communication
cable connected to the
central remote controller?
Check interface
P.C. board of outdoor
Defective Replacement