3-72
Check code
Operation cause
[95]
Communication alarm between
indoor and outdoor
1. Connection error of communication cable (PQ) between
indoor and outdoor
2. Connection error of connector for indoor communication,
P.C. board (MCC-1361) error
3. Connection error of connector for outdoor communication,
interface P.C. board error
NO
YES
YES
YES
NO
NO
YES
NO
YES
NO
YES
NO
Is there noise source, etc.?
Modify wiring of wire connector.
Modify communication cable.
Is power supply of
outdoor unit turned on?
Is there no miswiring/
disconnection of PQ
communication cable?
Is connection of CN101
connector of indoor main P.C. board
(MCC-1361) normal?
Is connection of
CN601 connector on outdoor
interface P.C. board normal?
Did a power failure occur?
Check indoor main
P.C. board (MCC-1361).
Defective Replacement
Turn on power supply of outdoor unit.
Clear the check code.
Check noise, etc., and remove it.
NOTE :
1. When turning on power supply of the indoor unit first of all, and pushing the START/STOP button before
power supply of the outdoor unit is turned on, “95” may be displayed. This is not abnormal, and then clear
the check code.
2. If “95” is displayed only on the 7 segment of the outdoor unit, it is considered that power supply of the
master outdoor unit is not switched on, or P.C. board error of the master outdoor unit occurs.
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...