3-95
Check code
Operation cause
[dE]
Indoor address undefined
1. Indoor unit in automatic addressing mode
2. Setting error of indoor main P.C. board (MCC-1361)
3. Indoor main P.C. board (MCC-1361) failure
4. Communication noise
While [dE] check code is displayed, wait for a moment. When the address is defined, the operation is
automatically reset. However, if the check code does not disappear 20 minutes have passed after power
supply was turned on, a fault is considered. Check the following items.
• Check failure of indoor main P.C. board (MCC-1361).
• Source check of communication noise
• Check faulty setting of jumper line on indoor main P.C. board (MCC-1361).
Check code
Operation cause
[dF]
Outdoor address undefined
1. Outdoor unit in automatic addressing mode
2. Defective indoor unit interface P.C. board
3. Communication noise
While this check code is displayed, wait for a moment. When the address is defined, the operation is auto-
matically reset. However, if the check code does not disappear 20 minutes have passed after power supply
was turned on, a fault is considered. Check the following items.
• Fault check of outdoor unit interface P.C. board
• Source check of communication noise between outdoor units
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...