3-30
Item
7. Defrost control
(Reverse
defrost method)
Operation explanation and applied data, etc.
(1) Start condition of defrost operation ...............................................
When 25 minutes has passed at the first time and 55 minutes at
the second time and later after the compressor was activated, by
counting the operation time when TE sensor detection
temperature became lower than –1°C in heating operation.
(2) Contents of control ........................................................................
1) Master outdoor unit
Drive the inverter with the minimum frequency. When
frequency of the inverter command is set to the minimum
frequency, the defrost signal is sent to the indoor unit and the
terminal outdoor unit. After then, turn off 4-way valve to stop
the outdoor fan. The upper limit of the inverter frequency is
90Hz during defrost control.
2) Terminal outdoor unit
• When the defrost conditions are satisfied, the defrost signal
is sent to the master outdoor unit.
• After receiving the defrost signal from the master outdoor
unit, turn off 4-way valve. After then, stop the outdoor fan.
• During defrost control, turn on all the fixed-speed
compressors.
(3) Stop conditions of defrost operation ..............................................
1) Common conditions
When the specified time has passed after 4-way valve was
turned off, the defrost operation completes based upon
conditions of TE sensor temperature detection value or Pd
pressure value. When 10 minutes have passed after start of
the defrost operation, finish the defrost operation manually.
2) Master outdoor unit
The operation shifts to the defrost stop control when the
common conditions of the defrost stop operation have been
satisfied and the defrost signal has completed from all the
terminal outdoor units.
3) Terminal outdoor unit
• When the common conditions of the defrost stop operation
have been satisfied, the defrost signal to the master outdoor
unit completes.
• The operation shifts to the defrost stop control when the
defrost stop conditions have been satisfied and the defrost
stop signal has been received from the master outdoor unit.
(4) Stop control of defrost operation
1) Master outdoor unit
Set the outdoor fan to the maximum No. of waves 5 seconds
after turning on 4-way valve. The heating fan control is
performed after then.
2) Master outdoor unit
• Drive the inverter with the minimum frequency. If the fixed-
speed compressor is off, turn on it, and keep ON status if
the fixed-speed compressor is on. When the terminal
outdoor unit is connected, send the defrost stop signal.
• After then, turn on 4-way valve to stop the defrost signal
which is being sent to the indoor unit.
3) Terminal outdoor unit
• Keep ON status of the fixed-speed compressor 1 and 2.
If they are off, turn on the compressor.
• Turn on 4-way valve after the specified time has passed
from when the defrost stop signal was received from the
master outdoor unit.
• After then, execute control for compressor capacity based
upon compressor start/stop ON/OFF signal from the master
outdoor unit.
Remarks
• When the conditions are
satisfied, each outdoor
unit starts defrost
operation concurrently.
• When the outdoor units
are combined, the defrost
operation continues
forcibly for 2 minutes if
the defrost operation has
started once.
• When the outdoor units
are combined, the fan
driving may be controlled
by Pd pressure during
defrost operation.
Содержание MMC-P0151H
Страница 198: ...3 195 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP06018 ...
Страница 206: ...3 203 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H8 ...
Страница 214: ...3 211 108 109 101 102 133 106 131 105 135 128 104 103 111 110 123 116 132 119 120 121 MMY MP0601H7 ...
Страница 216: ...TOSHIBA CARRIER CORPORATION 336 TADEHARA FUJI SHI SHIZUOKA KEN 416 8521 JAPAN ...