FOR SERVICE PERSONNEL ONLY

INVERTER SYSTEM MULTI TYPE
INDOOR UNIT
INSTALLATION MANUAL

HITACHI

MODEL

RAD-18QPB
RAD-25QPB
RAD-35QPB
RAD-50QPB

(Mark   is exclusive use tool for R410A)

l

  +  –  Screwdriver 

l

 Measuring Tape 

l

 Knife 

l

 Saw 

l

 ø 65mm Power Drill 

l

 Hexagonal Wrench 

Key (

 4mm) 

l

 Wrench (14, 17, 22, 26mm)  

Gas 

Leakage Detector 

l

 Pipe Cutter 

l

 Putty 

l

 Vinyl Tape   

 

l

 Pliers 

l

 Flare Tool  

 Vacuum Pump Adapter

   Manifold Valve     Charge Hose     Vacuum Pump 

l

 

 

Carefully read through the procedure before start-
ing installation work.

l

 

 

The sales agent should inform customers regarding 
the correct operation of installation.

l

 

 

Explanation for outdoor unit is in “How To Use” 
(Instruction Manual) that is packed with outdoor unit.

Tools Needed For Installation Work

WARNING ........ Incorrect methods of installation may cause death or serious injury.
CAUTION ......... Improper installation may result in serious consequence.
Make sure to connect earth wire.
This sign in the 

fi

 gures indicates prohibition.

!

!

SAFETY PRECAUTION

l

  Read the safety precautions carefully before operating the unit.

l

  The contents of this section are vital to ensure safety. Please pay special attention to the following sign.

Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating 
the unit as described in the user’s guide.

WARNING

!

l

  Please request your sales agent or quali

fi

 ed technician to install your unit. Water leakage, short circuit or 

fi

 re may occur if 

you do the installation work yourself.

l

 Unauthorized modi

fi

 cations to the air conditioner may be dangerous. If a breakdown occurs please call a quali

fi

 ed  air 

conditioner technician or electrician. Improper repairs may result in water leakage, electric shock and 

fi

 re,  etc.

l

  Be sure to connect the earth wire from the power supply wire to the outdoor unit and between the outdoor and indoor 

unit. Improper earthing may cause electric shock.

l

  Please observe the instructions stated in the installation manual during the process of installation. Improper installation may 

cause water leakage, electric shock and 

fi

 re.

l

  Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, 

the units may collapse and impose danger.

l

  Observe the rules and regulations of the electrical installation and the methods described in the installation manual when 

dealing with the electrical work. Use wire which is approved of

fi

 cial in your country. A short circuit and 

fi

 re may occur due 

to the use of low quality wire or improper work.

l

  Be sure to use the speci

fi

 ed wire for connecting the indoor and outdoor units. Please ensure that the connections are tight 

after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating 
and 

fi

 re.

l

  Please use the speci

fi

 ed components for installation work. Otherwise, the units may collapse or water leakage, electric shock 

and 

fi

 re may occur.

l

  When installing or transferring an air conditioner to another location, make sure that air other than the speci

fi

 ed  refrigerant 

(R410A) does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may 
increase abnormally high leading to possibility of unit rupture.

l

  Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with 

fi

 re, a poisonous 

gas may occur.

l

  After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas 

leaks into the room, coming into contact with 

fi

 re in the fan-driven heater, space heater, etc., a poisonous gas may occur.

l

  Be sure to use the speci

fi

 ed piping set for R410A. Otherwise, this may result in broken copper pipes or faults.

l

  When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, 

pressure in the refrigeration cycle may become abnormally high so that a rupture may be caused.

CAUTION

!

l

  A circuit breaker must be installed in the house distribution box for the direct connected power supply wire to the outdoor 

unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed. Without a circuit 
breaker, the danger of electric shock exists.

l

  Do not install the unit near a location where there is 

fl

 ammable gas. The outdoor unit may catch 

fi

 re  if 

fl

 ammable 

gas leaks around it. Piping shall be suitable supported with a maximum spacing of 1m between the supports.

l

  Please ensure smooth 

fl

 ow of water when installing the drain hose.

l

  An IEC approved power cord should be used. Power cord type: NYM.

THE CHOICE OF MOUNTING SITE

(Please note the following matters and obtain permission from 
customer before installation.)

!

WARNING

l

  The unit should be mounted at stable, non-vibratory 

location which can provide full support to the unit.

!

WARNING

l

  No nearby heat source and no obstruction near the air 

outlet is allowed.

l

  The clearance distances from top, right and left are 

speci

fi

 ed  in 

fi

 gure  below.

l

  The location must be convenient for water drainage and 

pipe connection with the outdoor unit.

l

  To avoid interference from noise, please place the unit 

and its remote controller at least 1m from the radio and  
television.

l

  To avoid any error in signal transmission from the remote 

controller, please put the controller far away from high-
frequency machines and high-power wireless systems.

Accessories to indoor Unit:

No.

Quantity

Item

1

2

3

4

5

6

7

8

Flare Insulator

Binder

4.0 x 10 Screw

Insulation Pipe

Aluminium Tape (large)

Band

Suspension Clamp (right, left) each

4.0 x 10 Screw

1

2

2

1

1

1

2

8

[Indoor unit installation]

CAUTION

Always install the indoor unit at level. If the 
indoor unit is inclined, water may leak.

!

Be sure to completely 
seal any gap with putty.

l

 The connecting pipe, 

irrespective of the size, 
should all be insulated 
with insulation pipe and 
then wrapped with vinyl 
tape. (The insulator will 
deteriorate if it is not 
wrapped with tape).

Drain pipe
Must be installed separately. 
Insulate indoor part of pipe to 
prevent condensation.

The indoor piping should 
b e   i n s u l a t e d   w i t h   t h e 
enclosed insulation pipe. (If 
the insulator is insuf

fi

 cient, 

please use commercial 
products.)

l

  “Height difference” and “Piping length” of Indoor and Outdoor unit are different by Outdoor unit.

 

Please refer to the installation manual in Outdoor unit.

<IA1171: A >

1. RECOMMENDATION  FOR  INSTALLATION

l

  The 

fi

 gures below are the recommended installation type for this duct model.

l

  All the optional parts mentioned for each installation type and screws should be purchased locally prior to the installation.

Full duct type

Semi duct type

Need optional parts
when installing full duct type (Local purchase)

Discharge grille

Chamber of discharge grille ø150mm

Chamber of discharge of unit side ø150mm

Chamber of suction of unit side ø150mm

Chamber of suction grille ø150mm

Suction grille with 

fi

 lter

Flexible duct ø150mm 1m
Flexible duct ø150mm 2m

2

1

Need optional parts
when installing semi duct type (Local purchase)

Discharge grille

Chamber of discharge grille ø150mm

Chamber of discharge of unit side ø150mm

Suction grille

Flexible duct ø150mm 1m
Flexible duct ø150mm 2m

Non duct type

2.  Installation procedure and notice

 

Select the installation location carefully for the split type 
air conditioner. It is very dif

fi

 cult to move a split type air 

conditioner after the 

fi

 rst installation. 

2.1 

Make a hole on the wall as shown in Fig. 2-1.

l

 The hole on the wall 

should be made 
with some inclination 
like Fig. 2-1 to keep 
the smooth 

fl

 ow  of 

condensed water.

2.2  Connecting pipe installation

 

l

  Seal the end of the pipes to prevent damage from 

moisture and water.

2.3  Drain pipe installation

 

l

  Use PVC pipe VP20 (O.D. 25mm) for drain pipe.

 

l

  You must roll an insulation (thickness 10mm or more) over the indoor section of the drain pipe.

 

l

  Position the drain pipe in the downward direction to enable free-

fl

 ow of water. Fix it with a hanger and avoid twisting the pipe as 

shown in Fig. 2-3.

2.4 Installation method of unit type

 

INSTALLATION OF FULL DUCT TYPE

l

 Select the indoor unit position, 

fi

 xing direction of air outlet so        

that cool/hot air reaches all the room. Standard position of 
the indoor unit is with the wall side on the ceiling.

l

  Remove the factory 

fi

 tted 

fi

 lter and 

fi

 lter holders before installing 

of full duct type.

l

 Secure the space for installation, inspection or servicing.

l

 Apply water-proof treatment to back surface of ceiling under the indoor unit, to prevent water drop.

l

 Do not allow any obstacle to block air 

fl

 ow within 1m of suction grille.

l

 Permissible length and bending of duct.

Discharging side duct

Suction side duct

Permissible length

4m or less added to suction side

1m or less

Bending

90° or less, 1 section

45° or less, 1 section

Other optional parts for display panel wired remote controller 
& wireless remote controller SPX-RCDA & SPX-RCKA1

Display panel 

1

Panel installation plate 

1

Panel cover 

1

Remote controller (wireless) 

1

Remote Controller Holder 

1

3.1 x 16 screw 

2

Wired Remote Controller with 2 screws 

1

Item

Quantity

No.

1

2

3

4

5

6

7

3

4

5

6

7

1

2

3

4

5

Need optional parts
when installing non duct type (Local purchase)

Discharge grille

Discharge duct

Suction grille

1

2

3

Electrical 
box

Air outlet

Filter

Wired 
remote 
controller

Air inlet

2 ~ 5mm

65mm

Outdoor 
side

Large diameter pipe

Small diameter pipe

„

 Insulation pipe

Stagnant water

No trap

No insulation

Do not do the installation as shown as above

Seal

Downward 1/25 ~ 1/100

Insulation

(Thickness 10mm or more)

Tape

(Unit : mm)

Fig. 2-1

Fig. 2-2

Fig. 2-3

Indoor 
side

GAS

INS RAD-18-25-35-50QPB (EN)   1

INS RAD-18-25-35-50QPB (EN)   1

12/19/14   9:42 AM

12/19/14   9:42 AM

Содержание RAD-18QPB

Страница 1: ...rom customer before installation WARNING l The unit should be mounted at stable non vibratory location which can provide full support to the unit WARNING l No nearby heat source and no obstruction near the air outlet is allowed l The clearance distances from top right and left are specified in figure below l The location must be convenient for water drainage and pipe connection with the outdoor un...

Страница 2: ...using 7 screws CAUTION Be sure to install the indoor unit level If the indoor unit is inclined water may leak If space between bottom surfaces of indoor unit and ceiling is not correct there may be a gap between grille and ceiling surface with consequent leakage of condensed water In case of wooden frame In case of steel frame INSTALLATION OF SEMI DUCT TYPE Opening on ceiling 96 Flexible duct Flex...

Страница 3: ... between bottom surfaces of ceiling and indoor unit is 58mm Select the indoor unit position fixing direction of air outlet so that cool hot air reaches all the room Do not allow any obstacle to block air flow within 1m of suction grille Use M10 bolt for suspension Opening of ceiling and suspension bolt position are as shown on the left Before installing the indoor unit prepare opening 960mm x 520m...

Страница 4: ...roller casing can be opened by pressing the slots with minus screw driver see below diagram Decide the fixing location of remote controller so that the length of wire shall be within 5 meters 4 3 Wind the inadhesive vinyl tape which is belonged from the pipe set around the refrigerating pipes and the connecting cord 4 4 Leakage checking of refrigerant at the coupling by gas leak detector or soapsu...

Отзывы: