<IA1171: A >

Outer 
Diameter
mm (inch)

6.35 (1/4")

9.52 (3/8")

12.70 (1/2")

15.88 (5/8")

1.0 ~ 1.5

1.0 ~ 1.5

1.0 ~ 1.5

1.0 ~ 1.5

Clutch type

A (mm)

1.5 ~ 2.0

1.5 ~ 2.0

1.5 ~ 2.5

1.5 ~ 2.5

Wing nut type

Thickness

(mm)

0.8

0.8

0.8

1.0

0.0 

~

 0.5

0.0 

~

 0.5

0.0 

~

 0.5

0.0 

~

 0.5

Flare tool for R410A

Clutch type

Conventional 

fl

 are  tool

(3)  Installation of suspension bolt

•  This is the same as for discharge/suction duct type. 

Follow instructions for discharge/suction duct type.

(4)  Preparation for installing indoor unit

•  Remove the screw 

ƒ

 of the electric box and then 

remove electric box.

•  Relocate the electric box with lead wires kept 

connected. Ensure the lead wire is positioned at the 
upper side, and hook the claw of electric box to side 
plate. Then 

fi

 x the electric box to the bottom of the 

indoor unit using 4 screws.

•  Install 4 suspension clamps at both sides of indoor unit, 

2 clamps at each side, using 8 tapping screws 

ˆ

.

(Since sizes of left and right clamps are different for 
certain parts, refer to diagram on the right.)

•  Install chamber of discharge of unit side on the indoor 

unit using 10 tapping screws.

(3)  Installation of suspension bolt

•  This is the same as for discharge/suction duct type. 

Follow instructions for discharge/suction duct type.

(4)  Preparation for installing indoor unit

•  Remove the screw 

ƒ

 of the electric box and then 

remove electric box.

•  Relocate the electric box with lead wires kept 

connected. Ensure the lead wire is positioned at the 
upper side, and hook the claw of electric box to side 
plate. Then 

fi

 x the electric box to the bottom of the 

indoor unit using 4 screws.

•  Install 4 suspension clamps at both sides of indoor unit, 

2 clamps at each side, using 8 tapping screws 

ˆ

.

(5)  Change of suction opening and 

fi

 lter 

position from bottom to back side

• Remove the 

fi

 lter from the bottom side of indoor 

unit by removing 8 screws from the 

fi

 lter holders.

•  Remove 6 screws from the back plate of the 

indoor unit.

(6)  Installation of indoor unit

•  Set nut and washer on suspension bolt and hook it 

to suspension clamp by lifting the indoor unit.

•  Make sure that indoor unit is kept at a straight level 

using a level or vinyl hose with water.

•  Fix the indoor unit so that the space between 

bottom surfaces of ceiling and indoor unit is 58mm.

2.5 Connection of the drain pipe

(1)  Securely glue connection part of drain hose and 

PVC pipe, using PVC adhesive.

(2)  Make sure to wrap generally-available insulator (10m 

or more of foamed polythene) around drain hose 
inside the house for insulation.

(3)  To check the drain and water leakage, after 

connecting power:

•  Add water to the water pan of the indoor unit as 

shown below.

(4)  Test run method



 

Turn power on.

‚ 

Remove lid of electric box and set the drain pump 
test run switch to TEST.

ƒ 

After checking the drainage, return the switch to 
NORMAL.

(5)  Perform test running of drain pump to check 

drainage operation.

2.6 Preparation of pipe

•  Use a pipe cutter to cut the copper pipe.

• Before 

fl

 aring, please put on the 

fl

 are nut.

•  Please use exclusive tool.

•  Then install the back plate at the bottom of indoor 

unit using 6 screws.

• Install 

fi

 lter at backside of indoor unit by 

fi

 xing it 

with 

fi

 lter holders (4 portions) using 8 screws.

• 

Chamber of discharge grille

(5)  Installation of indoor unit

•  Set nut and washer on suspension bolt and hook it to 

suspension clamp by lifting the indoor unit.

•  Make sure that indoor unit is kept at level using a level 

or vinyl hose with water.

•  Fix the indoor unit so that the space between bottom 

surfaces of ceiling and indoor unit is 58mm.

•  Select the indoor unit position, 

fi

 xing direction of air 

outlet so that cool/hot air reaches all the room.

•  Do not allow any obstacle to block air 

fl

 ow within 

1m of suction grille.

•  Use M10 bolt for suspension.
•  Opening of ceiling and suspension bolt position are 

as shown on the left.

•  Before installing the indoor unit, prepare opening 

960mm x 520mm on ceiling, and 868mm x 152mm 
on wall and arrange drain pipe, refrigerant pipe and 
connecting cord in their installation positions.

• For 

fi

 nishing of opening on ceiling and wall arrange 

with builder in detail.

•  Be sure to reinforce furring of ceiling (frame: ceiling 

joist and joist supporter) to maintain level of ceiling 
and prevent vibration of ceiling plate.

Refer to the installation manual of optional parts for 
installation of:
--Discharge grille chamber
--Suction grille
--Discharge grille
--Flexible duct

(1) Installation 

fi

 gure

(2) Opening on ceiling and suspension bolt position

INSTALLATION OF NON DUCT TYPE

CAUTION

!

•  Install the indoor unit in a straight level. If the 

indoor unit is inclined, water may leak.

•  If space between bottom surfaces of indoor 

unit and ceiling is not correct, there may be a 
gap between grille and ceiling surface, with 
consequent leakage of condensed water.

•  If gluing of drain hose and PVC pipe is too weak, 

water leakage may occur.

•  If checking of drainage is omitted, water leakage may 

occur.

•  If drain pump test run is left set to TEST, drain pump 

may malfunction.

CAUTION

CAUTION

!

!

•  Be sure to install the indoor unit level. If the 

indoor unit is inclined, water may leak.

•  If space between bottom surfaces of indoor 

unit and ceiling is not correct, there may be a 
gap between grille and ceiling surface, with 
consequent dropping of condensed water.

•  Jagged edge will cause leakage.
•  Point the side to be trimmed downwards during 

trimming to prevent copper chips from entering 
the pipe.

CAUTION

CAUTION

!

!

Ceiling

Above 200

Above 300

Front view

Plan view

Side view

Above 330

Above 300

Opening on ceiling

Suspension bolt 
(M10: Local purchase)

Reinforcement

Suspension bolt 
position 740

Indoor unit

Chamber of discharge 
of unit side

Screw

A level

Opening on ceiling

Suspension bolt (M10)
  (Local 

purchase)

Hexagon nut (M10)
  

(Local 

purchase)

Washer
(Local purchase)

58mm

Ceiling

(Unit : mm)

(Unit : mm)

Opening on ceiling 960

Opening on ceiling 520

Opening for discharge

Opening for discharge

Suspension bolt 347

Suspension bolt 790

Air deflector

Indoor unit

Discharge duct

Discharge duct

Discharge grille

Discharge grille

Above 300

Above 650

Above 300

Above 800

Above 300

Suction grille

Opening for discharge 960

Opening for discharge

Wall surface

Above 650

52 or less

Above 300

45 or less

Suspension bolt

Suspension bolt 
about 170

Suspension bolt 790

Indoor unit center

Indoor unit center

(View from the front)

(View from ceiling)

(Discharge side)

Front view

Plan view

Indoor unit

Back plate

(1) Bottom side suction opening

Filter holders

Filter holders

Filter

Filter

Back plate

Indoor unit

(2) Back side suction opening

A level

Opening on ceiling

Suspension bolt (M10)
  (Local 

purchase)

Hexagon nut (M10)
  

(Local 

purchase)

Washer
(Local purchase)

58mm

Ceiling

Drain hose

PVC pipe

PVC adhesive

Pump of oil stove

Pail

Water

Water pan

Trimming tool

Copper pipe

Die

Die

Copper pipe

Drain pump

Drain pump test switch (SW503)
      Test               Normal

‡

 Left side 

suspension clamp (2)

‡

 Right side 

suspension clamp (2)

Screw

3

Screw

8

Screw

3

Screw

8

‡

 Left side 

suspension clamp (2)

‡

 Right side 

suspension clamp (2)

Screw

3

Screw

8

Screw

3

Screw

8

INS RAD-18-25-35-50QPB (EN)   3

INS RAD-18-25-35-50QPB (EN)   3

12/19/14   9:42 AM

12/19/14   9:42 AM

Содержание RAD-18QPB

Страница 1: ...rom customer before installation WARNING l The unit should be mounted at stable non vibratory location which can provide full support to the unit WARNING l No nearby heat source and no obstruction near the air outlet is allowed l The clearance distances from top right and left are specified in figure below l The location must be convenient for water drainage and pipe connection with the outdoor un...

Страница 2: ...using 7 screws CAUTION Be sure to install the indoor unit level If the indoor unit is inclined water may leak If space between bottom surfaces of indoor unit and ceiling is not correct there may be a gap between grille and ceiling surface with consequent leakage of condensed water In case of wooden frame In case of steel frame INSTALLATION OF SEMI DUCT TYPE Opening on ceiling 96 Flexible duct Flex...

Страница 3: ... between bottom surfaces of ceiling and indoor unit is 58mm Select the indoor unit position fixing direction of air outlet so that cool hot air reaches all the room Do not allow any obstacle to block air flow within 1m of suction grille Use M10 bolt for suspension Opening of ceiling and suspension bolt position are as shown on the left Before installing the indoor unit prepare opening 960mm x 520m...

Страница 4: ...roller casing can be opened by pressing the slots with minus screw driver see below diagram Decide the fixing location of remote controller so that the length of wire shall be within 5 meters 4 3 Wind the inadhesive vinyl tape which is belonged from the pipe set around the refrigerating pipes and the connecting cord 4 4 Leakage checking of refrigerant at the coupling by gas leak detector or soapsu...

Отзывы: