172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
210
2. AT U
oFF
: PID control
on
: Start Autotuning
When Autotuning (AT) is finished, the control will automatically
return to “
oFF
.”
oFF
To display “Input 2_Autotunning (AT)”, choose “2-loop control/Differential
temperature control” in Function block No.58: Select function for Input 2
(Engineering mode), AND choose a setting other than “3 to 7 (Pressure control
operation [MC-
(V)COS(R)])” in Function block No.52: Input 2_Control action
(Engineering mode).
Input 1_AT bias [Setup Setting Mode: Setting group No. 53 (
Sn53
)]
Parameter symbol
Data range
Factory set value
1.
U
AT b
-(Input 1_Input span) to +(Input 1_Input span)
(When Control with PV select: -(PV select input span) to
+(PV select input span))
[Varies with the setting of the Decimal point position.]
0
To display “Input 1_AT bias”, choose a setting other than “3 to 7 (Pressure
control operation [MC-
(V)COS(R)])” in Function block No.51: Input 1_Control
action (Engineering mode).
Input 2_AT bias [Setup Setting Mode: Setting group No. 54 (
Sn54
)]
Parameter symbol
Data range
Factory set value
2. AT b
-(Input 2_Input span) to +(Input 2_Input span)
[Varies with the setting of the Decimal point position.]
0
To display “Input 2_AT bias”, choose “2-loop control/Differential temperature
control” in Function block No.58: Select function for Input 2 (Engineering mode),
AND choose a setting other than “3 to 7 (Pressure control operation [MC-
(V)COS(R)])” in Function block No.52: Input 2_Control action (Engineering mode)
Input 1_AT remaining time monitor [Setup Setting Mode: Setting group No.
53 (
Sn53
)]
Parameter symbol
Data range
Factory set value
1.A TT M
0 hours 00 minutes to 48 hours 00 minutes
To display “Input 1_AT remaining time monitor”, choose a setting other than “3
to 7 (Pressure control operation [MC-
(V)COS(R)])” in Function block No.51:
Input 1_Control action (Engineering mode).
Input 2_AT remaining time monitor [Setup Setting Mode: Setting group No.
54 (
Sn54
)]
Parameter symbol
Data range
Factory set value
2.A TT M
0 hours 00 minutes to 48 hours 00 minutes
To display “Input 2_AT remaining time monitor”, choose “2-loop control/
Differential temperature control” in Function block No. 58: Select function for Input
2
(Engineering mode), AND choose a setting other than “3 to 7 (Pressure control
operation [MC-
(V)COS(R)])” in Function block No.52: Input 2_Control action
(Engineering mode).
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...