172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
48
77
2.SVRd
Input 2_Setting change
rate limiter (down)
5)
★
0 to Input 2_Input span
0: No function
[Varies with the setting of the Decimal
point position.]
0
78
2.A/M.A
Input 2_Auto/Manual
transfer selection (Area)
6)
★
0: No transfer
1: Auto mode (bumpless)
2: Auto mode (bump)
3: Manual mode (bumpless)
4: Manual mode (bump)
0
79
2. MV.A
Input 2_Manipulated
output value (Area)
6)
★
-5.0 to +105.0%
[When settings either 2: Auto mode
(bump) or 4: Manual mode (bump) is
selected in Input 2_Auto/Manual transfer
selection (Area)]
-5.0
80
R/L.A
Remote/Local transfer
selection (Area)
7)
★
When “Remote setting input” is selected
at Select function for Input 2
8)
0: No transfer
1: Local mode
2: Remote mode
0
When “Cascade control” is selected at
Select function for input 2
9)
0: No transfer
1: Single control
2: Cascade control
When “Control with PV select” is
selected at Select function for input 2
10)
0: No transfer
1: Input 1
2: Input 2
When “2-loop control/Differential
temperature control” is selected at
Select function for input 2
11)
0: No transfer
1: 2-loop control
2: Differential temperature control
★
Data included in Memory area
1)
Displayed when "Soft start" is selected in "Soft start/setting change rate limiter selection" in Function block No. 70: Memory area
function (
AREA
).
2)
Displayed when "Setting change rate limiter" is selected in "Soft start/setting change rate limiter selection" in Function block No. 70:
Memory area function (
AREA
).
3)
Not displayed when "Pressure control operation [MC-(V)COS(R)]" is selected in "Input 1_Control action".
4)
Displayed when "2-loop control/Differential temperature control" or "Cascade control" is selected in "Select function for Input 2",
AND "Soft start" is selected in "Soft start/setting change rate limiter selection" in Function block No. 70: Memory area function
(
AREA
).
5)
Displayed when "2-loop control/Differential temperature control" or "Cascade control" is selected in "Select function for Input 2" AND
"Setting change rate limiter" is selected in "Soft start/setting change rate limiter selection" in Function block No. 70: Memory area
function (
AREA
).
6)
Displayed when "2-loop control/Differential temperature control" is selected in "Select function for Input 2" AND "Pressure control
operation [MC-(V)COS(R)]" is not selected in "Input 2_Control action".
7)
Displayed when one of "Remote setting input", "Cascade control", "Control with PV select", or "2-loop control/Differential
temperature control" is selected AND in the case of "2-loop control", "PID control" or "Heating/Cooling PID control" is selected in
both Input 1_ Control action and Input 2_Control action.
8)
Displayed when
“Remote setting input” is selected in “Select function for Input 2”.
9)
Displayed when “Cascade control” is selected in “Select function for Input 2”.
10)
Displayed when “Control with PV select” is selected in “Select function for Input 2”.
11)
Displayed when "2-loop control/Differential temperature control" is selected, AND in the case of "2-loop control", "PID control" or
"Heating/Cooling PID control" is selected in both Input 1_Control action and Input 2_Control action.
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...