172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
145
Details of functions assigned to DO1 to 4
Setting
Assigned functions
0
No assignment
1
Logic calculation output [Event, Input error status]
2
RUN state output
3
Input 1_Manual mode state output
4
Input 2_Manual mode state output
5
Remote mode state output (Cascade control state output, Output of differential
temperature control state, Input 2 state output of Control with PV select)
6
Input 1_Autotuning (AT) state output
7
Input 2_Autotuning (AT) state output
8
Output while Set value of Input 1 is changing
9
Output while Set value of Input 2 is changing
10
Output of the communication monitoring result
11
FAIL output
12
Input 1_Control error
13
Input 2_Control error
[Explanation of the setting]
Input 1_Control error: Turns ON when error (abnormality) occurs in Input 1_
Pressure control. This is only available when pressure control operation [MC-
(V)COS(R)] is selected for Input 1_Control action.
Input 2_Control error: Turns ON when error (abnormality) occurs in Input 2_
Pressure control. This is only available when pressure control operation [MC-
(V)COS(R)] is selected for Input 2_Control action.
Refer to [Explanation of the setting] in
“Details of functions assigned to OUT1 to
OUT3” for other settings.
Details of OUT1 to 3 as well as DO1 to 4 logic calculation selection
Multiple functions can be selected in the logic operation. The selected functions are
OR-
output. To select multiple functions, add the numbers of the desired functions.
Setting
Assigned functions
Example
To select Event 1 output and Input
1_Input error output high, set as follows.
・
Event 1 = 1
・
Input 1_Input error high = 16
1 + 16 = 17
So, set 17
0
No assignment
1
Event 1
2
Event 2
4
Event 3
8
Event 4
16
Input 1_Input error high
32
Input 1_Input error low
64
Input 2_Input error high
128
Input 2_Input error low
[Explanation of the setting]
Event:
Output turns on when the instrument is in the event state.
You also need to set Event assignment, Event type, Event hold action, Event
differential gap, Event timer, and Event set value.
Refer to 7.1 Using Event Function for details.
Input error high:
Output turns on when the Measured value (PV) exceeds the Input error
determination point (high).
Under the conditions of an available Input circuit error alarm, when the Measured
value of Input 2 goes over the Set value of the Input circuit error alarm and the
measured value of Input 1, the Input error high alarm of Input 1 will turn on.
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...