172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
144
[Explanation of the setting]
Input 1_Control output [heat-side] or [open-side]:
Assignable to Input 1. When Heating/Cooling PID control is selected for Input 1,
this output is used as heating output.
Input 1_Control output [cool-side] or [close-side]:
This output is available when Heating/Cooling PID control is selected for Input 1.
If Heating/Cooling PID control is selected, this output is used as a cooling output.
Input 2_Control output
Assignable to Input 2. This output is available when 2-loop control (including
Differential temperature control) or Cascade control is selected for Select function
for Input 2.
Retransmission output:
Retransmission output type needs to be specified later. Retransmission output
scaling is also available.
Refer to 6.3 Using Retransmission Output for Retransmission output.
Logic calculation output [Event, Input error status]:
Logic calculation needs to be specified separately. Multiple outputs can be output
from a single output terminal as logical
OR
relation.
Refer to the Logic calculation selection.
RUN state output:
Output turns on while the instrument is in RUN mode.
Input 1_Manual mode state output:
Output turns on while the Input 1 is in Manual mode.
Input 2_Manual mode state output:
Output turns on while the Input 2 is in Manual mode.
Remote mode state output (Cascade control state output, Output of differential
temperature control state, Input 2 state output of Control with PV select)
Output turns on while the instrument is in the remote mode, cascade control,
differential temperature control, or when Input 2 of Control with PV select is used.
Input 1_Autotuning (AT) state output:
Output turns on while the Input 1 is in the Autotuning (AT).
Input 2_Autotuning (AT) state output:
Output turns on while the Input 2 is in the Autotuning (AT).
Output while Set value of Input 1 is changing:
Output turns on while the Input 1_Set value (SV) is changing due to Soft start/
Setting change rate limiter.
Output while Set value of Input 2 is changing:
Output turns on while the Input 2_Set value (SV) is changing due to Soft start/
Setting change rate limiter.
Output of the communication monitoring result:
Valid only when the communication function is supplied. Output turns on if
improper communication continues for 10 seconds.
FAIL output:
Output turns on when the instrument is in FAIL state.
When FAIL is selected, the output terminal is fixed to de-energizing, and the
previous setting of energizing and de-energizing will be unavailable.
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...