172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
49
3.8 Setup Setting Mode [G]
3.8.1 Setting group No. 10: Display (
DSP
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Sn10
Setting group No. 10
This is the first parameter symbol of
Setting group No. 10
81
PVCY
Display update cycle
1: 50 ms*
2: 100 ms
3: 150 ms
4: 200 ms
5: 250 ms
6: 300 ms
7: 350 ms
8: 400 ms
9: 450 ms
10: 500 ms
1
* When
“Cascade control” or “2-loop control/
Differential temperature control
” is selected,
Display update cycle is 100 ms even when
“1”
is selected.
3.8.2 Setting group No. 21: Input 1 (
1.InP
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Sn21
Setting group No. 21
This is the first parameter symbol of
Setting group No. 21
82
1. Pb
Input 1_PV bias
-(Input 1_Input span) to +(Input 1_Input
span)
(When Control with PV select:
-(PV select input span) to +(PV select
input span))
[Varies with the setting of the Decimal
point position.]
0
83
1. DF
Input 1_PV digital filter
0.0 to 100.0 seconds
0.0: Filter OFF
0.0
84
1. PR
Input 1_PV ratio
0.500 to 1.500
1.000
85
1. PLC
Input 1_PV low input
cut-off
1)
0.00 to 25.00% of Input 1_Input span
(When Control with PV select: 0.00 to
25.00% of PV select input span)
0.00
1)
Displayed when Input 1 is Voltage/Current and Square root extraction is available.
3.8.3 Setting group No. 22: Input 2 (
2.InP
)
No.
Symbol
Name
Data range
Factory set
value
User set
value
Sn22
Setting group No. 22
1)
This is the first parameter symbol of
Setting group No. 22
86
2. Pb
Input 2_PV bias
1)
(RS bias)
2)
Input 2_PV bias
-(Input 2_Input span) to +(Input 2_
Input span)
RS bias
-(Input 1_Input span) to +(Input 1_
Input span)
[Varies with the setting of the Decimal
point position.]
0
87
2. DF
Input 2_PV digital filter
1)
(RS digital filter)
3)
0.0 to 100.0 seconds
0.0: Filter OFF
0.0
88
2. PR
Input 2_PV ratio
1)
(RS ratio)
4)
Input 2_PV ratio: 0.500 to 1.500
RS ratio: 0.001 to 9.999
1.000
89
2. PLC
Input 2_PV low input
cut-off
5)
0.00 to 25.00% of Input 2_Input span
(When Control with PV select: 0.00 to
25.00% of PV select input span)
0.00
1)
Not displayed when “No function” is selected in “Select function for Input 2.”
2)
Displayed as "RS bias" when "Remote setting input" is selected in Select function for Input 2.
3)
Displayed as "RS digital filter" when "Remote setting input" is selected in Select function for Input 2.
4)
Displayed as "RS ratio" when "Remote setting input" is selected in Select function for Input 2.
5)
Displayed when Input 2 is Voltage/Current and when Square root extraction is available. Not displayed when "No function" or
"Remote setting input" is slected in "Select function for Input 2."
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...