172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
244
3: kPaG
4: MPaG
When Input 2_Control type is set to 7 or 9:
10: mmHg/Torr
11: mbar
12: inHg
13: psi
14: kPa
NOTE: To use a pressure unit other than the valve coefficient
F indicated on the valve coefficient plate, refer to the
"Converting valve coefficient" section in "8.8 Using with MC-
COS/MC-VCOS" in the instruction manual
(parameters/functions) to convert the valve coefficient and
change the valve coefficient F along with valve coefficients A,
C, and E.
Valve coefficient value (A to F) is indicated in the valve coefficient plate
(attached) on the MC-(V)COS(R), which is also indicated on the valve
coefficient tag when the equipment is new.
To display “Input 2_Valve coefficient F”, choose “2-loop control/Differential
temperature control” in Function block No. 58: Select function for Input 2
(Engineering mode), AND choose “3 to 7 (Pressure control operation [MC-
(V)COS(R)])” or “8 and 9 (Temperature control operation [MC-(V)COS(R)])” in
Function block No.52: Input 2_Control action (Engineering mode).
Input 2_Pressure standard for Valve coefficient F [Engineering Mode:
Function block No. 54 (
Fn54
)]
Parameter symbol
Data range
Factory set value
2. GS L
0: Atmospheric (gauge) pressure standard
1: Absolute pressure standard
Same as pressure standard
for Input 1_Valve coefficient F
To display
“Input 2_Pressure standard for Valve coefficient F”, choose “2-loop
control/Differential temperature control” in Function block No. 58: Select function
for Input 2 (Engineering mode), AND choose “7 (Pressure control operation
[MC-
(V)COS(R)])” in Function block No.52: Input 2_Control action (Engineering
mode).
Input 2_Control valve selection [Engineering Mode: Function block No. 54
(
Fn54
)]
Parameter symbol
Data range
Factory set value
2. VS L
0: MC-VCOS(R)
1: PC-VCOS(R)
0
To display “Input 2_Control valve selection”, choose “2-loop control/Differential
temperature control” in Function block No. 58: Select function for Input 2
(Engineering mode), AND choose “7 (Pressure control operation [MC-
(V)COS(R)])” in Function block No.52: Input 2_Control action (Engineering
mode).
PC-VCOS(R) is an old model control valve for MC-
VCOS(R). Choose “1”
when PC-VCOS(R) is used with equipment.
Input 2_Pressure (temp) limiter [Engineering Mode: Function block No. 54
(
Fn54
)]
Parameter symbol
Data range
Factory set value
2. Pr L
When Input 2_Control type is set to 3 to 7:
Input 2_Input range low to Input 2_Input range high
When Input 2_Control type is set to 8:
Valve coefficient
Coefficient F = 0 (kg/cm
2
G): 0.00 to 99.99
When Input 2_Control type
is a setting other than 7: 0
When Input 2_Control type
is set to 7: Input 2_Input
NOTE
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...