172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
357
Input 2_Soft start time increase [Parameter setting mode: Parameter group
No. 70 (
Pn70
)]
Parameter symbol
Data range
Factory set value
2.S FT U
0 hours 00 minutes to 99 hours 59 minutes
0 minutes 00 seconds to 199 minutes 59 seconds
[The time unit depends on the setting of Soft start time unit.]
0:00
(0 minutes 00 seconds)
To display
“Input 2_Soft start time increase”, choose “2-loop control/Differential
temperature control” or “Cascade control” in Function block No. 58: Select
function for Input 2 (Engineering mode).
Input 1_Soft start time decrease [Parameter setting mode: Parameter group
No. 70 (
Pn70
)]
Parameter symbol
Data range
Factory set value
1.S FT d
0 hours 00 minutes to 99 hours 59 minutes
0 minutes 00 seconds to 199 minutes 59 seconds
[The time unit depends on the setting of Soft start time unit.]
0:00
(0 minutes 00 seconds)
Input 2_Soft start time decrease [Parameter setting mode: Parameter group
No. 70 (
Pn70
)]
Parameter symbol
Data range
Factory set value
2.S FT d
0 hours 00 minutes to 99 hours 59 minutes
0 minutes 00 seconds to 199 minutes 59 seconds
[The time unit depends on the setting of Soft start time unit.]
0:00
(0 minutes 00 seconds)
To display “Input 2_Soft start time decrease”, choose “2-loop control/Differential
temperature control” or “Cascade control” in Function block No. 58: Select
function for Input 2 (Engineering mode).
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...