172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
88
Function
block No. 31
Retransmission output 1 scale high
AHS1
Input 2_Measured value
(PV), Input 2_Local SV,
and Input 2_SV monitor
value: Input 2_Input
range high
Input 2_Deviation:
(Input 2_Input span)
4
Retransmission output 1 scale low
ALS1
Input 2_Measured value
(PV), Input 2_Local SV,
and Input 2_SV monitor
value: Input 2_Input
range low
Input 2_Deviation:
(Input 2_Input span)
4
Function
block No. 32
Retransmission output 2 scale high
AHS2
Same as Retransmission
output 1 scale high
4
Retransmission output 2 scale low
ALS2
Same as Retransmission
output 1 scale low
4
Function
block No. 33
Retransmission output 3 scale high
AHS3
Same as Retransmission
output 1 scale high
4
Retransmission output 3 scale low
ALS3
Same as Retransmission
output 1 scale low
4
Engineering
Mode
Function
block No. 41
Event 1 differential gap
EH1
TC/RTD inputs: 2
V/I inputs: 0.2
3
Function
block No. 42
Event 2 differential gap
EH2
3
Function
block No. 43
Event 3 differential gap
EH3
3
Function
block No. 44
Event 4 differential gap
EH4
3
Function
block No. 52
Input 2_Start determination point
2. P d A
3% of Input 2_Input span
Input 2_Level PID differential gap
2. L H S
TC/RTD inputs: 2
V/I inputs: 0.2
Function
block No. 58
Cascade_AT mode (master-side)
MAS.AT
TC/RTD inputs: 0
V/I inputs: 1
Cascade_AT mode (slave-side)
SLV.AT
Function
block No. 72
Input 2_Setting limiter high
2. S L H
Input 2_Input range high
Input 2_Setting limiter low
2. S L L
Input 2_Input range low
1)
When Input 2_Input type is changed.
Conditions:
1. "Select function for Input 2" is "Control with PV select."
2. A setting other than Control with PV select is selected for "Select function for Input 2"
3. Event type is a setting other than Manipulated output value AND "Select function for Input 2" is a setting other than "Control with PV
select," AND Event assignment is "Input 2."
4. Retransmission output is "Input 1_Measured value (PV)," "Input 1_Set value (SV)," or "Input 1_Deviation."
4.1.5 When Input 1_Control action (
1. OS
) is changed [Engineering Mode:
Function block No. 51]
The following parameters will be initialized. Some parameters may have
prerequisites for initialization. (See below for the conditions.)
Mode
Items
Symbol
Initial value
Condition
Parameter
Setting Mode
Parameter
group No. 51
Input 1_Proportional band [heat-side]
1. P
TC/RTD inputs: 30
V/I inputs: 3.0
Input 1_Integral time [heat-side]
1. I
240
Input 1_Derivative time [heat-side]
1. d
60
Input 1_Control response parameter
1. RPT
PID control or Position
proportioning PID
control: 0
Heating/Cooling PID
control: 2
Input 1_Proactive intensity
1.PACT
2
Input 1_Manual reset
1. MR
0.0
Input 1_FF amount
1. FF
0.0
Input 1_ON/OFF action differential gap
(upper)
1. OHH
TC/RTD inputs: 1
V/I inputs: 0.1
Input 1_ON/OFF action differential gap
(lower)
1. OHL
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...