172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
169
[Parameters to set up]
Auto/Manual transfer selection (Area)
This setting is used to select whether the mode should be transferred to Auto mode or
Manual mode at the time of Memory area selection. This setting is also used to select
balanceless bumpless action or bump action at the time of Auto/Manual transfer.
Manipulated output value (Area)
This setting is used to set a manipulated output value when Bump action is selected
at the time of Auto/Manual selection (area). This setting is used in Auto mode and
Manual mode in common.
There are several ways to select a memory area.
Refer to 10.3 Storing the Control Related Settings (Memory Area Function) or
the Quick Start Guide (172-65706M) for the selection by key operation. Refer to
5.2 Switching Functions Using Digital Inputs (DI) for the selection by Digital
input (DI).
Refer to 10.5 Executing Simple Program Operation or 10.6 Executing Simple
Sequence Operation for the selection by Memory area soak time.
Bumpless/Bump action by
“Auto/Manual transfer selection (Area)” has a priority
over the Bumpless/Bump action by
“Manual manipulated output value selection.”
Unavailable when “Pressure control operation [MC-(V)COS(R)]” is selected in
Control action.
Parameter setting
Manual manipulated output value selection [Engineering Mode: Function
block No. 50 (
Fn50
)]
Parameter symbol
Data range
Factory set value
MV T S
0: The last manipulated output value (Balanceless
bumpless function)
1: Manual manipulated output value
0
Input 1_Manual manipulated output value [Setup Setting Mode: Setting
group No. 51 (
Sn51
)]
Parameter symbol
Data range
Factory set value
1. M.M V
PID control, Position proportioning PID control:
Input 1_Output limiter low [heat-side] to Input 1_ Output
limiter high [heat-side]
Heating/Cooling PID control:
-(Input 1_Output limiter high [cool-side]) to +(Input 1_
Output limiter high [heat-side])
Pressure/Temperature control operation [MC-(V)COS(R)]:
Input 1_Output limiter low [heat-side] to whichever the smaller
value of either "calculated value from Input 1_Pressure
(temperature) limiter" or "Input 1_Output limiter high [heat-side]
PID control, Pressure or
Temperature control by MC-
(V)COS(R):
5.0
Heating/Cooling PID
control: 0.0
Heating/Cooling PID control has exceptional conditions as follows for the data range when:
(1) Input 1_Output limiter high [cool-side] is less than or equal to 0.0%
Input 1_Output limiter low [heat-side] is less than or equal to 0.0%: 0.0 % to +(Input 1_Output limiter high [heat-side])
Input 1_Output limiter low [heat-side] is less than or equal to 0.0%: Input 1_Output limiter low [heat-side] to Input 1_Output
limiter high [heat-side]
(2) Input 1_Output limiter high [heat-side] is less than or equal to 0.0%
Input 1_Output limiter low [cool-side] is less than or equal to 0.0%: -(Input 1_Output limiter high [cool-side]) to 0.0%
Input 1_Output limiter low [cool-side] is greater than 0.0%: -(Input 1_Output limiter high [cool-side]) to -(Input 1_Output limiter
low [cool-side])
(3) Fixed at 0.0% in the following cases:
Input 1_Output limiter high [cool-side] less than or equal to 0.0%, AND Input 1_Output limiter high [heat-side] less than or equal
to 0.0%
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...