5.3 Correcting Input
PV bias can be used for Input correction. The PV bias is used to compensate the
individual variations of the sensors or correct the difference between the Measured
value (PV) of other instruments.
Description of function
●
PV bias
PV bias adds bias to the Measured value (PV).
Setting example of PV bias:
When measuring the same type of load by using different sensors, the Measured
value (PV) will be displayed differently based on the features of sensors:
SC-F71 [A]: 200
C
SC-F71 [B]: 198
C
To correct the Measure value (PV) of SC-F71 [B], add bias of
2
C by PV bias:
Displayed value
Measured value (PV)
PV bias
198
C
2
C
200
C
●
PV ratio
PV ratio is a multiplier to be applied to the Measured value (PV).
Setting example of PV ratio:
PV ratio can be used to display 200 °C by adding 2 °C when the actual Measured
value (PV) is 198 °C but the displayed value remains 0 °C when the actual PV is
0 °C. (The displayed value changes from 0 °C to 2 °C by PV bias setting.)
Displayed value
Measured value (PV)
PV ratio = 198
C
1.010 = 199.98
C
SC-F71
[A]
SC-F71
[B]
200 °C
198 °C
Sensor A
Sensor B
Load A
Load B
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...