172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
57
150
1.P G D P
Input 1_Decimal point
position
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC input:
W5Re/W26Re, PR40-20: 0 (fixed)
Thermocouples other than those
shown above: 0 to 1
RTD input: 0 to 2
Voltage (V)/Current (I) input:
In case of Input data type 0: 0 to 4
In case of Input data type 1: 0 to 3
(When Control with PV select:
Decimal point position setting of Input 1
and Input 2 is compared and the smaller
will be used.)
Product
identificatio
n code
specified at
the time of
order.
For V/I
inputs: 1
151
1.P G S H
Input 1_Input range high
(Input 1_Input range low + 1 digit)
to Input 1_Maximum value of input range
[Varies with the setting of the Decimal
point position.]
When 3 to 7 (pressure control operation
[MC-(V)COS(R)]) is set to Input 1_Control
action, the set value for the parameter
should be entered with the same pressure
unit selected for Input 1_Valve coefficient
F.
Product
identificatio
n code
specified at
the time of
order.
For V/I
inputs:
100.0
152
1.P G S L
Input 1_Input range low
Input 1_Minimum value of input range
to (Input 1_Input range high - 1 digit)
[Varies with the setting of the Decimal
point position.]
When 3 to 7 (pressure control operation
[MC-(V)COS(R)]) is set to Input 1_Control
action, the set value for the parameter
should be entered with the same pressure
unit selected for Input 1_Valve coefficient
F.
Product
identificatio
n code
specified at
the time of
order.
For V/I
inputs: 0.0
153
1. P o V
Input 1_Input error
determination point (high)
Input 1_Input error determination point
(low) to Input 1_Input range high + (Input
1_5% of input span)
[Varies with the setting of the Decimal
point position.]
Input 1_
Input range
high +
(Input 1_
5% of input
span)
154
1. P U N
Input 1_Input error
determination point (low)
Input 1_Input range low - (Input 1_5% of
input span) * to Input 1_Input error
determination point (high)
[Varies with the setting of the Decimal
point position.]
* When Input type of Input 1 is RTD, low limit
value is about 2 Ohms. (Pt100: -245.5
C
[-409.8
F], JPt100: -237.6
C [-395.7
F])
Input 1_
Input range
low - (Input
1_5% of
input span)
155
1.T C J C
Input 1_Temperature
compensation calculation
2)
0: No temperature compensation calculation
1: With temperature compensation
calculation
1
156
1. b o S
Input 1_Burnout direction
3)
0: Upscale
1: Downscale
0
157
1. SQR
Input 1_Square root
extraction 1
4)
0: Unused
1: Used
0
158
1. INV
Input 1_Inverting input
4)
0: Unused
1: Used
0
1)
Displayed when Thermocouple (TC)/RTD is selected in "Input 1_Input type".
2)
Displayed when Thermocouple (TC) is selected in "Input 1_Input type".
3)
Displayed when "Thermocouple (TC) input" and "Low voltage input (0 to 100 mV DC, 0 to 10 mV DC) is selected in "Input 1_Input
type", AND a setting other than "Pressure control operation [MC-(V)COS(R)])" is selected in "Input 1_Control action".
4)
Displayed when "Voltage (V)/Current (I)" is selected in Input 1 AND "PID control" or "Heating/Cooling PID control" is selected in
"Input 1_Control action".
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...