172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
109
4: Four decimal places
TC input:
W5Re/W26Re, PR40-20: 0 (fixed)
Thermocouples other than those shown above: 0 to 1
RTD input: 0 to 2
Voltage (V)/Current (I) input: 0 to 4
Input 2_Input type is not displayed when
“No function” is selected in Function
block No. 58: Select function for Input 2 (Engineering mode). The setting cannot
be changed when Remote setting input and Control with PV select are set.
When Control with PV select is set in Function block No. 58: Select function for
Input 2 (Engineering mode), a smaller value (of Decimal point position setting for
Input 1 and Input 2) will be used.
Refer to 4. Parameters that are Initialized/Modified when Setting is Changed for
the parameters that are initialized or automatically converted when the Input
2_decimal point position is changed.
Input 1_Input range high [Engineering Mode: Function block No. 21 (
Fn21
)]
Parameter symbol
Data range
Factory set value
1.P GS H
(Input 1_Input range low + 1 digit) to Input 1_Maximum
value of input range
[Varies with the setting of the Decimal point position.]
Refer to the Input range table for the input range of each
input type.
Product identification code
specified at the time of order.
For unspecified V/I inputs: 100.0
Refer to “4. Parameters that are Initialized/Modified when Setting is Changed”
for the parameters that are automatically converted when the Input 1_Input
range high is changed.
When 3 to 7 (pressure control operation [MC-(V)COS(R)]) is set to Input
1_Control action, the set value for the parameter should be entered with
the same pressure unit selected for Input 1_Valve coefficient F.
Input 2_Input range high [Engineering Mode: Function block No. 22 (
Fn22
)]
Parameter symbol
Data range
Factory set value
2.P GS H
TC/RTD inputs and Voltage (V)/Current (I) inputs
(For other than Remote setting input):
(Input 2_Input range low
1 digit) to Input 2_Maximum
value of input range
[Varies with the setting of the Decimal point position.]
Voltage (V)/Current (I) inputs (For Remote setting input):
(Input 2_Input range low
1 digit) to Input 1_ Maximum
value of input range
[Varies with the setting of the Decimal point position.]
Refer to the Input range table for the input range of each
input type.
Same as Input 1_Input range
high
Not displayed when No function is selected in Function block No. 58: Select
function for Input 2 (Engineering mode).
Refer to “4. Parameters that are
Initialized/Modified when Setting is Changed” for the parameters that are
automatically converted when the Input 2_Input range high is changed.
When 3 to 7 (pressure control operation [MC-(V)COS(R)]) is set to Input
2_Control action, the set value for the parameter should be entered with
the same pressure unit selected for Input 2_Valve coefficient F.
NOTE
NOTE
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...