172-65710M-04 (SC-F71 Parameters/Functions) 23 Dec 2021
173
Manipulated output value at STOP
Manipulated output value at STOP is a function to produce the preset manipulated
output value at Control STOP. In the case of Heating/Cooling PID control,
Manipulated output value can be set on both sides of heating and cooling. Likewise,
in case of a dual output type, manipulated output value can be set on both sides of
Control output 1 and 2.
Parameter setting
Output action at control stop [Engineering Mode: Function block No. 30 (
Fn30
)]
Parameter symbol
Data range
Factory set value
S S
0 to 7
0: OFF
+1: Logic calculation output: Action continues
+2: Retransmission output: Action continues
+4: Instrument status output: Action continues
To select two or more functions, sum each value.
0
Input 1_Manipulated output value at STOP [heat-side] [Engineering Mode:
Function block No. 51 (
Fn51
)]
Parameter symbol
Data range
Factory set value
1. RM V
-5.0 to +105.0%
-5.0
Input 2_Manipulated output value at STOP [Engineering Mode: Function
block No. 52 (
Fn52
)]
Parameter symbol
Data range
Factory set value
2. RM V
-5.0 to +105.0%
-5.0
To display
“Input 2_Manipulated output value at STOP”, choose “2-loop
control/Differential temperature control
” in Function block No. 58: Select function
for Input 2 (Engineering mode).
Input 1_Manipulated output value at STOP [cool-side] [Engineering Mode:
Function block No. 56 (
Fn56
)]
Parameter symbol
Data range
Factory set value
1.R MV c
-5.0 to +105.0%
-5.0
To display
“Input 1_Manipulated output value at STOP [cool-side]”, choose
“Heating/Cooling PID control” in Function block No. 51: Input 1_Control action
(Engineering mode).
Содержание SC-F71
Страница 16: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 15 2 loop control Cascade control Control with PV select ...
Страница 17: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 16 ...
Страница 18: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 17 Differential temperature control ...
Страница 114: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 113 Setting procedure ...
Страница 131: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 130 Setting procedure ...
Страница 134: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 133 Setting procedure ...
Страница 141: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 140 Setting procedure ...
Страница 153: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 152 Setting procedure ...
Страница 158: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 157 Setting procedure ...
Страница 168: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 167 Setting procedure ...
Страница 172: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 171 Setting procedure ...
Страница 175: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 174 Setting procedure ...
Страница 180: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 179 Setting procedure ...
Страница 185: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 184 ...
Страница 199: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 198 Setting procedure ...
Страница 207: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 206 Setting procedure ...
Страница 236: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 235 Setting procedure Selecting Heating Cooling PID control ...
Страница 249: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 248 Setting procedure ...
Страница 280: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 279 Setting procedure ...
Страница 293: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 292 Checking PID values ...
Страница 303: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 302 Setting procedure ...
Страница 316: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 315 Setting procedure ...
Страница 320: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 319 Setting procedure ...
Страница 347: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 346 Operating procedure ...
Страница 359: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 358 Setting Procedure Setting Soft start function ...
Страница 388: ...172 65710M 04 SC F71 Parameters Functions 23 Dec 2021 387 Setting procedure ...