76 • Control Keypad
_____________________________________________________________________________________________
COMM.PARAMETERS
- **** -
Displays in MAXIMIZED MODE only
(refer to section
6.4.1 page 40 for changing mode)
Display and Default
Values
Range Description
S. LINK PAR. SAVE
DISABLE
ENABLE/
DISABLE
Enables parameter modification via serial communication
SER. LINK CONTROL
DISABLE
ENABLE/
DISABLE
Enables start, stop, reset etc… via serial communication.
Note:
When ID=126 control is disabled. In order to be able to control
the HRVS-DN ID must be set to 1-125.
MODBUS TIME OUT
OFF
Do not change this parameter! Must be set to OFF.
FRONT COM ADDRES
OFF
OFF,1 – 247
Future enhancement
STORE ENABLE
COMM. PARAMETERS
Notes:
(1) Same as STORE ENABLE MAIN & PROTECT page 57.
(2) After changing communication parameters and storing them, control power
must be switched off and on to load new communication parameters.
7.8.10
Comm. Parameters – Page 7 – With the Optional DeviceNet PCB
COMM.PARAMETERS
- **** -
Displays in MAXIMIZED MODE only
(refer to section
6.4.1 page 40 for changing mode)
Display and Default
Values
Range Description
COMM. PROTOCOL
DEVICENET
MODBUS/
POFIBUS/
DEVICENET
Sets HRVS-DN’s communication protocol.
Operational when the optional communication PCB is installed.
BAUD RATE
AUTO
User can not change BAUD RATE value.
PARITY CHAECK
AUTO
Do not change this parameter! Must be set to AUTO.
DEVICENET ID
SET MANUALLY
SET
MANUALLY,
1-63
Sets the DeviceNet network ID.
When set to SET MANUALLY the ID is determined by the
encoders mounted on the DeviceNet optional PCB installed in
the control module.
S. LINK PAR. SAVE
DISABLE
ENABLE/
DISABLE
Enables parameter modification via serial communication
SER. LINK CONTROL
DISABLE
ENABLE/
DISABLE
Enables start, stop, reset etc… via serial communication
MODBUS TIME OUT
OFF
Do not change this parameter! Must be set to OFF.
FRONT COM ADDRES
OFF
OFF,1 – 247
Future enhancement
STORE ENABLE
COMM. PARAMETERS
Notes:
(1) Same as STORE ENABLE MAIN & PROTECT page 57.
(2) After changing communication parameters and storing them, control power
must be switched off and on to load new communication parameters.