165 • HRVS-DN Communication (DeviceNet™)
_______________________________________________________________________________________________
Figure 57 - Data rate (Baud rate) rotary switch layout
Rotary switch S1 (BAUD) is used to select the DeviceNet Baud Rate. The valid range of baud rates is 1
(125K), 2 (250K), 5 (500K), and P (programmable). All values P and above set the baud rate to the last baud
rate the device was powered up at and allow software configuration tools to modify the baud rate.
Factory default settings for the rotary switches are typically Address 63, 125K.
18.1.6
LED Indicators
The DeviceNet Gateway provides support for three LEDs: Serial Status (Modbus Diagnostic), Network
Status, and Module Status. The LED on the right indicates the current Serial or Modbus Diagnostic status.
The operation of the Modbus LED is described in Table 1.
Table 1
Modbus Diagnostic Status LED
Color State
Indication
None Off
No
power
Red Flashing
Modbus
Timeout
Orange Flashing
Modbus
Error
Green Flashing
Normal
operation
The LED in the middle indicates the Network Status. The operation of the Network Status LED is described
in Table 2.
Table 2
DeviceNet Network Status LED
Color State
Indication
None Off No
Power
Red
Solid Unrecoverable
Fault
Flashing
Recoverable Fault
I/O Connection Timed Out
Green
Solid
Normal runtime operation
Flashing
Device is idle or not allocated
to a master
Red / Green
Alternating
Identify (Offline Connection
Set)
The LED on the left indicates the Module Status. The operation of the Module Status LED is described in
Table 3.
Table 3
DeviceNet Module Status LED
Color State
Indication
None Off No
Power
Red
Solid Unrecoverable
Fault
Flashing Recoverable
Fault
Green
Solid Normal
operation
Flashing Not
Used
Red / Green
Alternating
Not used
125Kb
250Kb
500Kb
PGM
DATA RATE