![Solcon HRVS-DN series Скачать руководство пользователя страница 170](http://html1.mh-extra.com/html/solcon/hrvs-dn-series/hrvs-dn-series_instruction-manual_1314370170.webp)
170 • HRVS-DN Communication (DeviceNet™)
_____________________________________________________________________________________________
18.7.3
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get_Attribute_Single
10
HEX
No
Yes
Set_Attribute_Single
18.8
Control Supervisor Object (29HEX - 1 Instances)
18.8.1
Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data Value
Access
Rule
1 Revision
UINT
1 Get
18.8.2
Instance Attributes (Instance 1)
Attribute
ID
Name DeviceNet
Data Type
Data
Value
Access
Rule
Modbus
Register
3 Run1
(Forward)
BOOL 0 Get
/
Set
Bit 2: 40752
Bit 8-15: 0x5A
4 Run2
(Reverse)
BOOL 0 Get
/
Set
Always 0
7 Running1
(Forward)
BOOL
0
Get
Bit 11: 40257
9
Ready
BOOL
0
Get
Bit 5: 40257
10
Faulted
BOOL
0
Get
Bit 15: 40257
11
Warning
BOOL
0
Get
Bit 6: 40257
15
Ctrl From Net
BOOL
1
Get
Always 1
100
Control Word
UINT
0
Get /
Set
40752
(Read always 0-
since register is
not readable)
18.8.3
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
05
HEX
No
Yes
Reset
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
18.9
Modbus / Serial Object (65HEX – 1 Instance)
18.9.1
Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data Value
Access
Rule
1 Revision
UINT
1 Get
18.9.2
Instance Attributes (Instance 1)
Attribute
ID
Name DeviceNet
Data Type
Data Value Access
Rule
1
Modbus Slave ID (1-247)
USINT
1
Get /
Set
10
2 Baud
Rate
0 = 4800
1 = 9600
2 = 19200
USINT 2
Get
/
Set
10
3 Parity
0 = 8N
1 = 8E
2 = 8O
USINT 1
Get
/
Set
10
10
Timeout (milliseconds)
(10ms – 60000ms)
UINT 500 Get
/
Set
10
10
Stored to NVRAM