![Solcon HRVS-DN series Скачать руководство пользователя страница 167](http://html1.mh-extra.com/html/solcon/hrvs-dn-series/hrvs-dn-series_instruction-manual_1314370167.webp)
167 • HRVS-DN Communication (DeviceNet™)
_______________________________________________________________________________________________
18.5
Assembly Object (04HEX – 4 Instances)
18.5.1
Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data
Value
Access
Rule
1 Revision
UINT 2 Get
2 Max
Instance
UINT 112
Get
100 Input
Index
60 = Instance 60
61 = Instance 61
100 = Instance 100
USINT
2
Get / Set
5
101
Input Size (in bytes)
UINT
1
Get
102 Output
Index
112 = Instance 112
USINT
0
Get / Set
6
103
Output Size (in bytes)
UINT
1
Get
18.5.2
Output (O2T) Instance Attributes – Register 40752
Attribute
ID
Name DeviceNet
Data Type
Data
Value
Access Rule
3
Output Data
USINT[]
0
Get/Set
18.5.2.1
Output Instance 112 (0x70 – Attribute 3) – Control Output
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
0
1
0
1
1
0
1
0
1
Reset Reserved
Reserved
Dual
Adjust
Start/Stop
Relay
Reserved Reserved Reserved
18.5.3
Input (T20) Instance Attributes – Register 40257
Attribute
ID
Name DeviceNet
Data Type
Data
Value
Access
Rule
3
Input Data
USINT[]
0
Get
18.5.3.1
Input Instance 60 (0x3C) – Basic Softstart Input
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At
Reference
Reserve
d
Reserve
d
Reserve
d
Reserve
d
Running
1
Reserve
d
Faulted /
Trip
18.5.3.2
Input Instance 61 (0x3D) – Extended Softstart Input
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At
Reference
Reserved
Control
From
Net
Ready Running2 Running1 Warning
Faulted /
Trip
5 Stored to NVRAM
6 Stored to NVRAM