67 • Control Keypad
_______________________________________________________________________________________________
7.8.4
Stop Parameters – Page 3
STOP PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
(refer to section
6.4.1 page 40 for changing mode)
Display and Default
Values
Range Description
SOFT STOP CURVE
1 (STANDARD)
0 (BASIC)/
1
(STANDARD)/
2 !!/
3 !!/
4 !!/
5 (TORQUE)/
Sets SOFT STOP CURVE.
Refer to section
7.8.4.1 on page 68.
STOP TACHO. GAIN
0(MIN. GAIN)
0 (MIN. GAIN)/
1 !!/
2 !!/
3 !!/
4 !!/
5 !!/
1!!
represents the 2nd level TACHO GAIN
2!!
represents the 3rd level TACHO GAIN…..
5!!
represents the 6th level TACHO GAIN.
Notes:
(1) This parameter will appear only if the optional PCB is
installed and dip switch # 2 is set to on. Refer to section
6.4.2 on
page 41 for dip switch setting details.
(2) Tacho Feedback is operational in its basic form. Additional
curves except for the basic linear curve are optional.
(3) Consult the factory for the correct tacho selection and
mechanical installation.
DEC. TIME
0 SEC.
0–30sec.
Note:
The range of
the DEC.
TIME can be
extended to
0-90 sec. by
using the
EXTENDED
SETTING as
described in
section
6.4.4
page 42.
Sets DECELERATION TIME of the motor.
Used for controlled deceleration of high friction loads.
Determines the motor’s voltage ramp down time.
Note:
The HRVS-DN operates with a Bypass Contactor. The Bypass
Contactor is controlled by the HRVS-DN’s End of Acceleration
relay. Upon soft stop initiation the End of Acceleration relay is
de-energized, the load is transferred to the HRVS-DN, and
voltage begins ramping down.
FINAL TORQUE
0 (MIN.)
0 (MIN.) – 10
(MAX.)
Sets FINAL TORQUE during soft stop.
Determines torque towards the end of a soft stop.
If the current still flows after speed is softly reduced to zero, you
should increase the FINAL TORQUE setting.