70 • Control Keypad
_____________________________________________________________________________________________
7.8.5
Dual Adjustment Parameters – Page 4
DUAL ADJUSTMENT
PARAMETERS
Displays in MAXIMIZED MODE only
(refer to section
6.4.1 page 40 for changing mode)
Display and Default
Values
Range Description
DA: INIT. VOLT.
30%
10-50%
After reaching 50% the
display changes to:
DA: INITIAL CURRENT
100-400%.
Note:
The range of the DA:
INITIAL VOLTAGE can be
extended to
10-80% by using the
EXTENDED SETTING as
described in section
6.4.4
page 42.
Sets motor’s INITIAL STARTING VOLTAGE
in DA
mode.
(Motor’s
torque
is directly proportional to the
square of the voltage)
Refer to section
7.8.3 on page 60 parameter:
INITIAL VOLTAGE
DA: INIT. CURRENT
100%
DA: CUR. LIMIT
400% OF FLA
100-400%.
Note:
The range of the DA:
CURRENT LIMIT can be
extended to
100-700% by using the
EXTENDED SETTING as
described in section
6.4.4
page 42.
Sets motor’s highest current during starting
in DA
mode.
Refer to section
7.8.3 on page 60 parameter:
CURRENT LIMIT.
DA: ACC. TIME
10 SEC.
1-30sec.
Note:
The range of the DA: ACC.
TIME can be extended to
1-90 sec. by using the
EXTENDED SETTING as
described in section
6.4.4
page 42.
Sets ACCELERATION TIME of the motor
in DA
mode.
Refer to section
7.8.3 on page 60 parameter: ACC.
TIME.
DA: DEC. TIME
0 SEC.
0–30sec.
Note:
The range of the DA: DEC.
TIME can be extended to
0-90 sec. by using the
EXTENDED SETTING as
described in section
6.4.4
page 42.
Sets DECELERATION TIME of the motor
in DA
mode.
Refer to section
7.8.4 on page 67 parameter: DEC.
TIME.
DA: MOTOR FLA
150 AMP.
33-100% of STARTER FLC Sets motor’s FLA (Full load Ampere)
in DA mode.
Refer to section
7.8.2 on page 53 parameter:
MOTOR FLA.
STORE ENABLE
D. ADJ PARAMETERS
Same as STORE ENABLE MAIN & PROTECT page
57.