17 • Technical Data
_______________________________________________________________________________________________
4.4
HRVS-DN Selection
The HRVS-DN should be selected in accordance with the criteria of motor current and starting conditions.
4.4.1
Motor Current and Starting Conditions
Select the HRVS-DN according to the motor's Full Load Ampere (FLA) - as indicated on its nameplate (even if
the motor will not be fully loaded).
Soft Starter Full Load Current (FLC) must be
≥
Motor’s Full Load Ampere (FLA).
The HRVS-DN is designed to operate under the following maximum conditions:
Ambient
Temperature
[
°
C]
Max. Starting Current
[A]
Max. Starting
Time at 400%
FLC
[sec]
50 400%xFLC 30
Max. starts per hour: 2 starts per hour at maximum ratings.
4.4.2
PIV (Peak Inverse Voltage)
Thyristors PIV rating, internal circuitry and insulation define the following voltage levels:
2,300V, 3,300V, 4,160V, 6,600V, 10,000V, 11,000V, 13,800V and 15,000V.
Each soft starter is suitable for 50/60Hz.
PIV level is rated at 3 times the rated voltage or higher.