157 • HRVS-DN Communication (Profibus protocol)
_______________________________________________________________________________________________
17.7
Numbers of actual data Register for (decimal)
Number Parameter
Name
Description
1
Logic Status
Logic status of HRVS-DN. 1 indicates:
d15: HRVS-DN
Tripped.
d14: Motor
Stopped.
d13:
Motor in Soft Stop Process.
d12:
Motor in Start Process.
d11:
Motor is Running.
d10:
Motor is running with Closed By_Pass.
d9:
Up_To_Speed. Like d10 and I reduced (once) below 115% of
FLA.
d8: Reserved.
d7: Dual_Adjust
On.
d6..d0: Reserved.
Note: After by-pass is closed, trip (d15) and running (d11), can be ON
together. See Trip_after_By-Pass setting parameter at fault parameters
page.
2
Hardwired inputs
Discrete Hardwired control inputs:
d15..d8: Reserved.
d7:
External fault 2, Terminal 20.
d6:
External Fault 1,Terminal 19.
d5: Reserved.
d4:
Programmable Input , Terminal 8
d3:
Programmable Input, Terminal 7
d2:
Start Input.
Terminal 6
d1:
Soft Stop Input.
Terminal 5
d0:
Stop Input.
Terminal 4
3
Relays
d0 - Immediate, d1- End Of Acc, d2 - Fault relay
4
Voltage
Line voltage, % of rated voltage.
5
I1_amp
Current of phase 1, Ampere.
6
I2_amp
Current of phase 2, Ampere.
7
I3_amp
Current of phase 3, Ampere.
8
Reserved
9
Dip_Switch
d15..d8: Reserved.
d7: Setting
Lock -
(right-most)
d6: Enlarged
Setting
Ranges
d5: Language
Selection.
d4: Language
Selection.
d3:
Reserved - Must be set to Off.
d2:
Generator Starting - Set to Off.
d1:
Tacho feedback available (1).
d0:
Min (off) / Max display pages- (left most)
10
Phase_Sequence
1: Correct Phase seq. 0 : Wrong Phase Seq.
11
Motor Insulation R
Motor Insulation Resistance [KOhm]
12
Reserved
13
Reserved
14
Reserved
15
Power
Power consumption [KW]
16
Reactive Power
Reactive Power consumption [KVAR]
17
Power Factor
Power Factor * 100
18
Time Since Last Start
Elapsed minutes since last start
19
Frequency Frequency
[tenth
Hz]
20
Reserved
21
Reserved
22
Reserved
23
Reserved
24
Reserved
25
Logic Status at Power
Fail
Logic Status at Control Pwr Supply turn off.
26
Total Run Time
Total Hours of Running Motor.
27
Total Starts
Total Number Of Start
28
Last start period
Duration of last start, Seconds
29
Last start peak I
Peak current during last starting process