163 • HRVS-DN Communication (Profibus protocol)
_______________________________________________________________________________________________
Parameter
#
Range
Default
Ser. Link Control
85
0 (Disable), 1 (Enable)
0 (Disable control)
Modbus Time Out
86
1..247 & (248= Off)
248 (Off)
Front Com Address
87
1..600 & (601= Off)
601 (Off) (Off) (Tenth Sec)
Reserved 88
Modbus_#_Array
89..108 # of parameter
Defaults # are:
1 - Logic Status
5 – I1
6 – I2
7 – I3
4 – Voltage
2 – Ctrl-In
3 – Ctrl_Out (relays)
15 – Power
17 – Power Factor
19 – Frequency
10 – Phase Sequence
26 – Total Run Time
27 – Total Starts
31 – Total Trips
28 – Last Start Period
29 – Last Start Peak I
32 – Last Trip Number
33 – Pre Trip I
39 – Thermal Capacity
11 – Insulation Resistance
17.15
Time Parameters
Parameter
#
Range
Default
Clk Hour
130
0 – 23
Set here, Read at actual # 41
Clk Minute
131
0 – 59
Set here, Read at actual # 42
Clk Month
132
1 – 12
Set here, Read at actual # 43
Clk Day
133
1 – 31
Set here, Read at actual # 44
Clk Year
134
0 – 99
Set here, Read at actual # 45