64 • Control Keypad
_____________________________________________________________________________________________
START PARAMETERS
- **** -
Displays in MINIMIZED MODE and MAXIMIZED MODE
Display and Default
Values
Range Description
RUN CONTACT DLY
5 SEC.
0-120sec.
After reaching
120 seconds,
keep pressing for
10 seconds the
key and
only
if optional Relay
PCB is installed
the display
changes to:
TURN BYPASS
ON AT
120-300%.
Sets time delay for End of Acceleration relay to close after
completion of starting process.
End of Acceleration relay can signal that motor is at its RUN
position which can be used for motor loading.
TURN BYPAS ON AT
120 % OF FLA
For information on TURN BYPAS ON AT and MIN TIME TO
BYPS refer to section
7.8.3.2 on page 66.
MIN TIME TO BYPS
3 SEC.
3-60sec.
STORE ENABLE
START PARAMETERS
Same as STORE ENABLE MAIN & PROTECT page 57.