174 • HRVS-DN Communication (DeviceNet™)
_____________________________________________________________________________________________
Attribute
ID
Name Range
Default
Value
Access
Rule
Modbus
Address
12 Unbalance
Trip
10-100,
101 = Off
20 (%)
Get/Set
40012
13 Unbalance
Delay
1-60
5
(Second
)
Get/Set 40013
14
Ground Fault Trip
10-100,
101 = Off
20 (% of
FLA)
Get/Set 40014
15
Ground Fault Delay
1-60
5
(Second
)
Get/Set 40015
16
Under voltage Trip
50-90
70 (%)
Get/Set
40016
17
Under voltage Delay 1-100
5
(Second
)
Get/Set 40017
18
Overvoltage Trip
110-125
120 (%) Get/Set
40018
19 Overvoltage
Delay
1-10
2
(Second
)
Get/Set 40019
18.11.3
Common Services
Service
Code
Implemented for
Service Name
Class Level
Instance Level
0E
HEX
Yes
Yes
Get Attribute Single
10
HEX
No
Yes
Set Attribute Single
18.12
Start Settings Object (72HEX – 1 Instance)
18.12.1
Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data Value
Access
Rule
1 Revision
UINT
1 Get
18.12.2
Instance Attributes (Instance 1)
Attribute
ID
Name Range Default
Value
Access
Rule
Modbus
Address
1
Soft Start Curve 0-11 (6-11 are for
Tacho only)
1
(Standard
)
Get/Set 40025
2
Pulse Level
70 (%of FLA) –
700 (%of FLA)
70% of
FLA
Get/Set 40026
3
Pulse Time
0-10 (Tenth
Seconds)
0 (No
Pulse)
Get/Set 40027
4 Initial
Voltage/
Initial Current
10-80 /
100-400 % of
FLA
100 % of
FLA
Get/Set 40028
5
Current Limit
100-700
400 (% of
FLA)
Get/Set 40029
6 Acceleration
Time
1-90 10
(Seconds)
Get/Set 40030
7
Max. Start Time 1-250
30
(Seconds)
Get/Set 40031
8 Number
Of
Starts
1-10 & (11 = off)
1
Get/Set 40032
9 Starts
Period
1-60
20
(Minutes)
Get/Set 40033
10
Start Inhibit
1-60 minutes
15
(Minutes)
Get/Set 40034
11 Run
Contact
Delay
0-120 seconds
5
(Seconds)
Get/Set 40035