101 • High-Pot Test of the HRVS-DN Cabinet
_______________________________________________________________________________________________
You can perform a Megger test (5kVDC) between the three phases connected together as one group
and ground. This Megger test should give a very high resistance result.
You can also perform a Megger test between the three phases. To do this you must connect L1B-U,
L2B-V, L3B-W.
Since the EPT-Tx is connected between the phases, the following resistances are be expected (all
values are ±5%):
HRVS-DN Rated
Voltage
L1 – L2
L2 – L3
L1 – L3
2.3kV 670K
Ω
4M
Ω
4.67M
Ω
3.3kV 1M
Ω
6M
Ω
7M
Ω
4.16kV 1.33M
Ω
8M
Ω
9.13M
Ω
6.6kV 2M
Ω
12M
Ω
14M
Ω
11.2
High-Pot Test in HRVS-DN up to 6.6kV, EPT-Tx Not Connected
High-pot test procedure for L1 (refer to
Figure 40
):
Dismantle the EPT-Tx
Short circuit the L1B and U busbars of phase L1.
Short circuit the L2B and V busbars of phase L2.
Short circuit the L3B and W busbars of phase L3.
Short circuit input-output phases of the Line Contactor.
Connect to ground L2 and L3
Connect the ground cable of the High-pot tester to cabinet ground (earth).
Connect the live cable of the High-Pot tester to the soft starter busbars of L1.
Set the tester to the correct testing voltage, as specified above. Perform the test for 1 minute.
Figure 40 – HRVS-DN up to 6.6kV – EPT-Tx not Connected Preparations for High-pot Test, Testing L1
High-pot test procedure for L2 (refer to
Figure 41
):
Dismantle the EPT-Tx
Short circuit the L1B and U busbars of phase L1.
Short circuit the L2B and V busbars of phase L2.
Short circuit the L3B and W busbars of phase L3.
Short circuit input-output phases of the Line Contactor.
Connect to ground L1 and L3
Connect the ground cable of the High-pot tester to cabinet ground (earth).
Connect the live cable of the High-Pot tester to the soft starter busbars of L2.