SIPART DR20
Project Planning Manual
Planning example
S1
Fixed setpoint control, controlled variable from four-wire
transmitter, position feedback from electronic position
transmitter (EPT)
The controlled variable x from the transmitter is applied
to analog input AE1, the position feedback from the
electronic position transmitter is applied to analog input
AE2 of the controller. The programming for both inputs
corresponds to a signal range of 0 to 20 mA.
The transmitter and electronic position transmitter are
connected to external power supplies.
The alarm circuit monitors the negative deviation Xd for
max./min. deviations (set parameters A2 and A1 !).
W
X
y
Drive
Y
R
Setting of configuring switches: S2 = 2 or 3, S32 = 1
Please refer to the remarks on page 108 and the note on page 15 !
AE1
AE2
BE
BA
L+
GND GND
L
1
2
3
4
5
6
7
8
SIPART DR20 S
6DR2001-1 (AC 230 V)
6DR2001-2 (AC 115 V)
6DR2001-4
(UC 24 V)
1
2
3
4
1
2
3
4
1
2
3
4
PE
N
L
AC 115 V
AC 230 V
⎫
⎬
⎭
PE
N
UC 24 V
L
⎫
⎬
⎭
Slot 3 GW
Slot 2 AE4
Slot 1 AE3
-
∆
y
+
∆
y
9
10
5
M1
A1
R1
A2
M2
not equipped
Option module
6DR2801-8A
M
M/A
S
E
L
N
EPT
+
-
y
R
X
not equipped
I
Power supply
125
Содержание SIPART DR20
Страница 1: ...s Compact Controller SIPART DR20 Project Planning Manual 02 05 Order No 6ZB5600 0AAO2 0BA0 ...
Страница 2: ...Project Planning Manual SIPART DR20 empty page 2 ...
Страница 82: ...Project Planning Manual SIPART DR20 SIPART Bus Fig 5 12 SES bus driver remote system wiring diagram 82 ...
Страница 111: ...SIPART DR20 Project Planning Manual Empty page 111 ...