SIPART DR20
Project Planning Manual
3
1
2
4
6DR2800-8J
+
-
49.9
Ω
U
AE3 / AE4
+
-
6
M
Standard controller
0 to + 10 V
AE +
AE -
Connection circuit of signal converter 6DR2800-8J as voltage input for a non-floating voltage source of 0 to +10 V. The possible drop on
the M bar enters the measurement as an error.
3
1
2
4
6DR2800-8J
+
-
49.9
Ω
U
AE3 / AE4
+
-
6
M
Standard controller
AE +
AE -
0 to - 10 V
Connection circuit of signal converter 6DR2800-8J as voltage input for a non-floating voltage source of 0 to - 10 V whilst avoiding
voltage drops on the M bar
3
1
2
4
6DR2800-8J
+
-
49.9
Ω
U
AE3 / AE4
+
-
6
M
Standard controller
0 to + 10 V
AE +
AE -
Connection circuit of signal converter 6DR2800-8J as voltage input for a floating voltage source of 0 to + 10 V.
Fig. 5/5
Wiring of module 6DR2800-8J for voltage signals