Technical specifications
12.2 General technical specifications
Drive converter cabinet units
480
Operating Instructions, 07/07, A5E00288214A
Order no.
6SL3710-...
Power [kW]
Output current
at 1.25 kHz [A]
Derating factor
at 2.5 kHz
Derating factor
at 5 kHz
Supply voltage 500 – 690 V 3 AC
7LG28-5AA0
75
85
89%
60%
7LG31-0AA0
90
100
88%
60%
7LG31-2AA0
110
120
88%
60%
7LG31-5AA0
132
150
84%
55%
7LG31-8AA0
160
175
87%
60%
7LG32-2AA0
200
215
87%
60%
7LG32-6AA0
250
260
88%
60%
7LG33-3AA0
315
330
82%
55%
7LG34-1AA0
400
410
82%
55%
7LG34-7AA0
450
465
87%
55%
7LG35-8AA0
560
575
85%
50%
7LG37-4AA0
710
735
79%
55%
7Lg38-1AA0
800
810
95%
55%
7LG38-8AA0
900
910
87%
55%
7LG41-0AA0
1000
1025
86%
50%
7LG41-3AA0
1200
1270
79%
40%
For pulse frequencies in the range between the fixed values, the relevant derating factors
can be determined by means of linear interpolation.
The following formula applies for this:
Example:
The derating factor is required for when X
2
= 2 kHz for 6SL3710-1LE41-0AA0.
X
0
= 1.25 kHz, Y
0
= 100%, X
1
= 2.5 kHz, Y
1
= 87%, X
2
= 2 kHz, Y
2
= ??
N+]
N+]
N+]
N+]
N+]
N+]
<
'HUDWLQJIDFWRU
3XOVH
N+]
N+]
N+]
N+]
f
100 %
50 %
75 %
25 %
60 %
87 %
?? %
Figure 12-1 Calculating derating factors by means of linear interpolation
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...