Setpoint channel and closed-loop control
7.3 V/f control
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
267
Table 7-1
p1300 V/f characteristics
Parameter
value
Meaning
Application / property
0
Linear characteristic Standard with variable voltage boost
V
n
0
f
n
V
f
S
1
Linear characteristic
with flux current
control (FCC)
Characteristic that compensates for voltage
losses in the stator resistance for static /
dynamic loads (flux current control FCC).
This is particularly useful for small motors,
since they have a relatively high stator
resistance.
9
9
U
S
S
I
PD[
/RDGFXUUHQW
GHSHQGHQW
2
Parabolic
characteristic
Characteristic that takes into account the
motor torque curve (e.g. fan/pump).
•
Quadratic characteristic (f² characteristic)
•
Energy saving because the low voltage
also results in small currents and losses.
V
n
0
f
n
V
f
S
3
Programmable
characteristic
Characteristic that takes into account the
motor/machine torque characteristic.
V
V
p1325
f1
p1320
max
r0071
p1327
p1323
p1321
0
f2
p1322
f3
p1324
f4
p1326
f
r1315
fmax
p1082
5
Precise frequency
drives
Characteristic (see parameter value 0) that takes into account the technological
particularity of an application (e.g. textile applications):
•
Whereby current limitation (Imax controller) only affects the output voltage and not
the output frequency.
•
By disabling slip compensation.
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...