Functions, monitoring, and protective functions
9.4 Extended functions
Drive converter cabinet units
378
Operating Instructions, 07/07, A5E00288214A
Flying referencing
The "on-the-fly referencing" mode (also known as post-referencing, positioning monitoring),
which is selected using a "1" signal at binector input p2597 (select referencing type), can be
used in every mode (jogging, traversing block and direct setpoint input for positioning/setup)
and is superimposed on the currently active mode. Flying referencing can be selected both
with incremental and absolute measuring systems.
With "flying referencing" during incremental positioning (relative), you can select whether the
offset value is to be taken into account for the travel path or not (p2603).
"Flying referencing" is activated by a 0/1 edge at binector input p2595 (start homing). The
signal in binector input p2595 (start homing) must be set during the entire referencing
process otherwise the process is aborted.
Status bit r2684.1 (passive/flying referencing active) is linked with binector input p2509
(activate measurement probe evaluation). It activates measurement probe evaluation.
Binector inputs p2510 (measurement probe selection) and p2511 (measurement probe edge
evaluation) can be used to set which measurement probe (1 or 2) and which measurement
edge (0/1 or 1/0) is to be used.
The measurement probe pulse is used to supply connector input p2660 (home measurement
value) with the measurement via parameter r2523. The validity of the measurement is
reported to binector input p2661 (measurement valid feedback) via r2526.2.
Note
The following must always apply to the "Flying referencing mode" windows:
p2602 (outer window) > p2601 (inner window).
See function diagram 3614 for more information on the "Flying referencing mode" function.
The following then happens:
●
If the drive has not yet been homed, status bit r2684.11 (reference point set) is set to "1".
●
If the drive has already been homed, status bit r2684.11 (reference point set) is not reset
when starting flying referencing.
●
If the drive has already been homed and the position difference is less than the inner
window (p2601), the old actual position value is retained.
●
If the drive has already been homed and the position difference is more than the outer
window (p2602), warning A07489 (reference point offset outside window 2) is output and
the status bit r2684.3 (pressure mark outside window 2) set. No offset to the actual
position value is undertaken.
●
If the drive has already been homed and the position difference is more than the inner
window (p2601) and less that the outer window (p2602), the actual position value is
offset.
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...