Technical specifications
12.3 Technical specifications
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
489
Table 12-15 Version A, 660 V – 690 V 3 AC, part 3
Category
Unit
Order No. 6SL3710-
7LH32-6AA0
7LH33-3AA0
7LH34-1AA0
Rated motor output
kW
250
315
400
Rated input voltage
V
660 V to 690 V 3 AC ± 10% (-15% < 1 min)
Rated input current
1)
A
242
304
375
Rated output current
A
260
330
410
Base-load current I
L2)
A
250
320
400
Base-load current I
H3)
A
233
280
367
Max. output frequency
4)
Hz
100
100
100
Power loss
kW
11.1
12.5
17.7
Cooling air requirement
m³/s
1.19
1.19
1.96
Sound pressure level at 50/60 Hz dB(A)
75/77
75/77
77/79
Line connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 95
4 x 240
4 x (500)
M12 (2 holes)
2 x 120
4 x 240
4 x (500)
M12 (2 holes)
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
Motor connection
Recommended: DIN VDE
5)
Maximum: DIN VDE
AWG/MCM
Fixing screw
mm
2
mm
2
2 x 95
2 x 185
2 x (350)
M12 (2 holes)
2 x 120
2 x 240
2 x (500)
M12 (2 holes)
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
Protective conductor connection
Fixing screw
M12 (2 holes)
M12 (2 holes)
M12 (2 holes)
Approx. weight (standard version) kg
892
892
1716
Frame sizes
Active Interface Module
Active Line Module
Motor Module
GI
GX
GX
GI
GX
GX
HI
HX
HX
Dimensions (standard version)
Width x height x depth
mm
1600 x 2,000 x 600
1600 x 2,000 x 600
2200 x 2,000 x 600
Recommended protection
Line protection
(with option L26)
Rated current
Frame size to DIN 43620-1
Line and semi-cond. protection
(without option L26)
Rated current
Frame size to DIN 43620-1
A
A
3NA3354-6
355
3
3NE1331-2
350
2
3NA3365-6
500
3
3NE1334-2
500
2
3NA3365-6
500
3
3NE1334-2
500
2
1)
The currents are based on a power factor of cos ϕ = 1 and include 10 A for the external auxiliary equipment (as used, for
example, with options L19 or B03).
2)
The base-load current (I
L
) is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
3)
The base-load current (I
H
) is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
4)
Maximum output frequency at factory-set default pulse frequency (for information on increasing the output frequency,
see "Functions, monitoring and protective functions/Increasing the output frequency"; for information on derating data, see
"Derating data").
5)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
(National Electrical Code) or CEC (Canadian Electrical Code) standards.
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...