Electrical installation
4.6 Power connections
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
57
4.6.4
Adjusting the internal power supply (-A1-T10)
A transformer is installed in the line connection module (-A1-T10) for the internal 230 V AC
power supply for the cabinet. The location of the transformer is indicated in the layout
diagrams supplied.
When delivered, the taps are always set to the highest level. The primary terminals of the
transformer may need to be reconnected to the existing supply voltage.
The supply voltage assignments for making the appropriate setting on the transformer for the
internal power supply are indicated in the following tables.
NOTICE
If the terminals are not reconnected to the actual supply voltage, the internal power supply
will not be correct.
Table 4-7
Supply voltage assignments for the internal power supply (380 V – 480 V 3 AC)
Supply voltage range
Tap
Matching transformer taps (-A1 -T10) LH1 – LH2
342 V to 390 V
380 V
1 - 2
391 V to 410 V
400 V
1 – 3
411 V to 430 V
415 V
1 – 4
431 V to 450 V
440 V
1 – 5
451 V to 470 V
460 V
1 – 6
471 V to 528 V
480 V
1 – 7
Table 4-8
Supply voltage assignments for the internal power supply (660 V – 690 V 3 AC)
Supply voltage range
Tap
Matching transformer taps (-A1 -T10) LH1 – LH2
591 V - 630 V
600 V
1 – 12
631 V - 680 V
660 V
1 – 14, terminals 12 and 13 are jumpered
681 V - 759 V
690 V
1 – 15, terminals 12 and 13 are jumpered
Table 4-9
Supply voltage assignments for the internal power supply (500 V – 690 V 3 AC)
Supply voltage range
Tap
Matching transformer taps (-A1 -T10) LH1 – LH2
450 V – 515 V
500 V
1 - 8
516 V – 540 V
525 V
1 – 9
541 V – 560 V
550 V
1 – 10
561 V – 590 V
575 V
1 – 11
591 V – 630 V
600 V
1 – 12
631 V – 680 V
660 V
1 – 14, terminals 12 and 13 are jumpered
681 V – 759 V
690 V
1 – 15, terminals 12 and 13 are jumpered
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...