Diagnosis / faults and alarms
10.2 Diagnosis
Drive converter cabinet units
412
Operating Instructions, 07/07, A5E00288214A
Control Interface Board – Interface Module in the Power Module (-G1)
Table 10-4 Description of the LEDs on the Control Interface Board
LED state
H200
H201
Description
OFF
OFF
The electronics power supply is missing or lies outside the permissible tolerance
range.
OFF
The component is ready for operation and cyclic DRIVE-CLiQ communication is taking
place.
Orange
The component is ready for operation and cyclic DRIVE-CLiQ communication is taking
place.
The DC link voltage is present.
Green
Red
The component is ready for operation and cyclic DRIVE-CLiQ communication is taking
place.
The DC link voltage is too high.
Orange
Orange
DRIVE-CLiQ communication is being established.
Red
---
At least one fault is pending on this component.
Note:
LED is driven irrespective of the corresponding messages being reconfigured.
0.5 Hz flashing
light:
green/red
---
Firmware is being downloaded.
2 Hz flashing
light:
green/red
---
Firmware download is complete. Wait for POWER ON.
2 Hz flashing
light:
green/orange
or
red/orange
---
Detection of the components via LED is activated (p0124).
Note:
Both options depend on the LED status when module recognition is activated via
p0124 = 1.
WARNING
Hazardous DC link voltages may be present at any time regardless of the status of the
"H201" LED.
The warnings on the components must be observed.
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...