Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
425
Maintenance and servicing
11
11.1
Chapter content
This chapter provides information on the following:
●
Maintenance and servicing procedures that have to be carried out on a regular basis to
ensure the availability of the cabinet units.
●
Exchanging device components when the unit is serviced
●
Forming the DC link capacitors
●
Upgrading the cabinet unit firmware
●
Loading the new operator panel firmware from the PC.
DANGER
Before carrying out any maintenance or repair work on the de-energized cabinet unit,
wait for 5 minutes after switching off the supply voltage. This allows the capacitors to
discharge to a harmless level (< 25 V) after the supply voltage has been switched off.
Before starting work, you should also measure the voltage after the 5 minutes have
elapsed. The voltage can be measured on DC link terminals DCP and DCN.
DANGER
When the external power supply for individual options (L50 / L55) or the external 230 V
AC auxiliary supply is connected, dangerous voltages are still present in the cabinet unit
even when the main circuit breaker is open.
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...