![Siemens SINAMICS S150 Скачать руководство пользователя страница 502](http://html.mh-extra.com/html/siemens/sinamics-s150/sinamics-s150_operating-instructions-manual_378226502.webp)
Appendix
A.2 Parameter macros
Drive converter cabinet units
502
Operating Instructions, 07/07, A5E00288214A
Sink
Source
Parameter
Description
DO Parameter
Description
DO
p2051[4]
CI: PROFIBUS PZD send word
Vector r0082
P-act
Vector
p2051[5]
CI: PROFIBUS PZD send word
Vector r2131
FAULT
Vector
p2080[0]
BI: PROFIBUS send status word 1
Vector r0899[0]
Ready to power up
Vector
p2080[1]
BI: PROFIBUS send status word 1
Vector r0899[1]
Ready
Vector
p2080[2]
BI: PROFIBUS send status word 1
Vector r0899[2]
Operation enabled
Vector
p2080[3]
BI: PROFIBUS send status word 1
Vector r2139[3]
Fault
Vector
p2080[4]
BI: PROFIBUS send status word 1
Vector r0899[4]
No OFF2
Vector
p2080[5]
BI: PROFIBUS send status word 1
Vector r0899[5]
No OFF3
Vector
p2080[6]
BI: PROFIBUS send status word 1
Vector r0899[6]
Power-on inhibit
Vector
p2080[7]
BI: PROFIBUS send status word 1
Vector r2139[7]
Alarm present
Vector
p2080[8]
BI: PROFIBUS send status word 1
Vector r2197[7]
Setpoint/actual value deviation in
tolerance
Vector
p2080[9]
BI: PROFIBUS send status word 1
Vector r0899[9]
Control from PLC
Vector
p2080[10] BI: PROFIBUS send status word 1
Vector r2199[1]
Comparison value reached
Vector
p2080[11] BI: PROFIBUS send status word 1
Vector r1407[7]
M/I/P limiting not active
Vector
p2080[12] BI: PROFIBUS send status word 1
Vector 0
Vector
p2080[13] BI: PROFIBUS send status word 1
Vector r2129[14]
No alarm for motor overtemperature
Vector
p2080[14] BI: PROFIBUS send status word 1
Vector r2197[3]
Clockwise
Vector
p2080[15] BI: PROFIBUS send status word 1
Vector r2129[15]
No alarm for therm. overload of power
unit
Vector
p2088
PROFIBUS Invert status word
Vector B800h
Vector
p2128[14] Select fault/alarm code for trigger
Vector 7910
Alarm, motor overtemperature
Vector
p2128[15] Select fault/alarm code for trigger
Vector 5000
Alarm for therm. overload of power
unit
Vector
p2153
Speed actual value filter time constant Vector 20 ms
Vector
p0840[0]
ON/OFF 1
A_INF r0863.1
Energize line contactor
Vector
p2105
BI: 3. Acknowledge faults
A_INF r1214.3
Automatic restart status – set
acknowledgement command
Vector
p1207
BI: WEA link, following DO
A_INF r1214.2
Automatic restart status – restart
active
Vector
p4053[0]
TM31 analog inputs, smoothing time
constant
TM31 0 ms
TM31
p4053[1]
TM31 analog inputs, smoothing time
constant
TM31
TM31
p4056[0]
TM31 analog inputs, type
TM31 2
Current 0...20 mA
TM31
p4056[1]
TM31 analog inputs, type
TM31 2
Current 0...20 mA
TM31
p4076[0]
TM31 analog outputs, type
TM31 0
Current 0...20 mA
TM31
p4076[1]
TM31 analog outputs, type
TM31 0
Current 0...20 mA
TM31
p4071[0]
Signal analog output 0
TM31 r0063
Actual speed smoothed
TM31
p4071[1]
Signal analog output 1
TM31 r0068
Absolute current actual value
TM31
p4100
TM31 temperature evaluation, sensor
type
TM31 0
(Factory setting)
TM31
p4102[0]
TM31 temperature evaluation
fault/alarm threshold
TM31 251°C
Message being generated
TM31
p4102[1]
TM31 temperature evaluation
fault/alarm threshold
TM31 251°C
Message being generated
TM31
Содержание SINAMICS S150
Страница 2: ......
Страница 6: ...Preface Drive converter cabinet units 6 Operating Instructions 07 07 A5E00288214A ...
Страница 14: ...Table of contents Drive converter cabinet units 14 Operating Instructions 07 07 A5E00288214A ...
Страница 28: ...Device overview 2 5 Type plate Drive converter cabinet units 28 Operating Instructions 07 07 A5E00288214A ...
Страница 519: ......
Страница 520: ...Siemens AG Automation and Drives Large Drives P O Box 4743 90025 NÜRNBERG GERMANY www ad siemens com A5E00288214A ...